Inspections for the day of: Thursday, September 27, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01608 Electrical Rough-In9/26/20189/27/20189/27/2018 3:06:39 PMPPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Discussed equipotential bonding, How to bond window frames in contact with water and 3' around equipment and disconnects serving equipment. Uderground complete for E.O. Wilson bldg rough in ok cover
ELE18-01989 Final9/26/20189/27/20189/27/2018 1:59:49 PMPPASS
Phone #: ###-#### Inspection requested via web by michael hunt Final ok
ELE18-03710 Temporary Service9/27/20189/27/20189/27/2018 1:14:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Perez
Contact to change cord to trailer, as per 400.5(A)- 3 current carrying conductor cord 35 amp max for #8 cord.
Only feeds job trailer, no temp receptacles. t/s u/g n ok
ELE18-00298 Final9/26/20189/27/20189/27/2018 10:50:08 AMACANC
Mike Phone #: ###-####
Job already finalled in march, contact has no idea why job was requested.
ELE18-03707 Electrical Rough-In9/26/20189/27/20189/27/2018 10:07:36 AMAFAIL
Corbin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
210.52(B)(2)- Small appliance branch circuits shall have no other outlets. Tapped off kitchen receptacle to feed light over sink.
300.4- Nail plates needed where bored holes do not maintain 1 1/4" from framing surface.
310.15(B)(16)- 14ga wire tapped off 20 amp branch circuit. 15 amp max on 14ga wire.
334.30- NM cable shall be supported at intervals not to exceed 4 1/2 and secure with in 12" of a box.
Looks like someone other than electical contractor may have done some work.
ELE18-03691 Electrical Rough-In9/26/20189/27/20189/27/2018 9:22:27 AMANR
contact name Wes Powell
Underground inspection Phone #: ###-#### Inspection requested via web by Deb Gooden
Had trouble with equipment, ground ring not complete yet.
ELE18-02064 Final9/26/20189/27/20189/27/2018 9:04:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok