ELE18-02986
| Final | 9/27/2018 | 9/27/2018 | 9/28/2018 6:42:24 AM | P | CANC |
|
|
Kelly Phone #: ###-####
|
ELE18-02986
| Final | 9/27/2018 | 9/27/2018 | 9/27/2018 3:43:58 PM | P | FAIL |
|
|
Kelly Phone #: ###-#### 210.11C2 and C3. Laundry room and Bath shall have 20Amp Dedicated circuits. ( Washer was moved from kitchen closet to back room. Needs updated circuitry and removed from bath circuit.) 314.20 Boxes set back more than 1/4in shall have extension rings. (All Devices in tile) 406.12 All dwelling unit receps shall be Tamper proof. (Dining and Front room)
|
ELE18-03490
| Electrical Rough-In | 9/27/2018 | 9/27/2018 | 9/27/2018 2:34:00 PM | P | PASS |
|
|
Need ceiling grid rough-in cover Phone #: ###-#### Inspection requested via web by Brad Girard Conferance room and 2 offices only rest is exhisting. ok to cover
|
ELE18-03678
| Rough-In Permanent Service | 9/27/2018 | 9/27/2018 | 9/27/2018 2:19:37 PM | P | PASS |
|
|
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|
ELE18-03632
| Temporary Service | 9/27/2018 | 9/27/2018 | 9/27/2018 1:33:48 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Corrections made t/s u/g n ok
|
ELE18-03575
| Rough-In Permanent Service | 9/27/2018 | 9/27/2018 | 9/27/2018 1:31:51 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Corrections made rough in ok p/s u/g n ok
|
ELE18-03635
| Permanent Service | 9/24/2018 | 9/27/2018 | 9/27/2018 1:01:25 PM | P | PASS |
|
|
There will be guys there working. If you have any questions please feel free to contact Fred ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Check sub panel at rough in for seperation of grounds. p/s o/h rec ok
|
ELE18-03088
| Electrical Rough-In | 9/27/2018 | 9/27/2018 | 9/27/2018 12:33:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling rough in main Dining area ok to cover
|
ELE18-02836
| Rough-In Permanent Service | 9/27/2018 | 9/27/2018 | 9/27/2018 11:33:30 AM | P | PASS |
|
|
It is open. If you have any questions, please call Tony at ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clayton Morgan Check house UFER connection at final. UFER is directly behind House panel. (NEC 250.32) Garage and house. Rough in ok.. p/s o/h n ok
|
ELE18-02836
| Electrical Rough-In | 9/27/2018 | 9/27/2018 | 9/27/2018 11:31:32 AM | P | CANC |
|
|
It is open. If you have any questions, please call Tony at ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clayton Morgan
|
ELE18-03640
| Rough-In Permanent Service | 9/26/2018 | 9/27/2018 | 9/27/2018 11:31:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
|
ELE18-03568
| Final | 9/26/2018 | 9/27/2018 | 9/27/2018 10:39:01 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Jesse Fuentes No access. Nobody home.
|
ELE18-03222
| Final | 9/26/2018 | 9/27/2018 | 9/27/2018 9:49:42 AM | A | PASS |
|
|
Access is best through either side gate. 2 levels added on rear of house. Phone #: ###-#### Inspection requested via web by David McClellan Final ok
|
ELE18-03375
| Electrical Rough-In | 9/26/2018 | 9/27/2018 | 9/27/2018 9:29:31 AM | A | PASS |
|
|
Wall rough in inspection for B17C Executive Suites Contact Pierce Bouge Thank you Phone #: ###-#### Inspection requested via web by Tom Betty Discussed Requirments of 210.71B1 and 2. Furniture receps will make up quantity needed in Large meeting room. Will need 3 floor receps in Large room and 1 in smaller room. Walls only ok to cover
|