Inspections for the day of: Tuesday, September 28, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01974 FIRE-Final Inspection9/27/20049/28/20049/28/2004 12:00:00 AMAFAIL
Relocate duct smoke detectors above return air round duct and provide sample tubes. This is for spaces 6421 and 6423. 9/28/2004 10:03:54 AM
MIS04-00002 FIR-Final9/27/20049/28/20049/28/2004 12:00:00 AMAPASS
Fire life safety finaled 9/27/2004 2:59:46 PM
BLD02-03033 FIRE-Final Inspection9/28/20049/28/20049/28/2004 12:00:00 AMAPASS
Fire life safety finaled
BLD03-01124 FIRE-Final Inspection9/28/20049/28/20049/28/2004 12:00:00 AMAFAIL
At 6513 - test duct smoke detector and provide approved hardware on restroom doors. At 6515 - test duct smoke detector and provide sticker at door. At 6517 test duct smoke detector and provide approved hardware on restroom doors
BLD02-00966 FIRE-Conference9/28/20049/28/20049/28/2004 12:00:00 AMPDONE
Told owner the last item I needed was the fire hydrant installed as shown on the approved plans. He said he is working with United Water to get it done. 9/28/2004 3:38:55 PM
FIR04-00463 INSP-Supply line flush9/28/20049/28/20049/28/2004 12:00:00 AMPCANC
contractor did not have valve key so no flush was done 9/28/2004 4:32:46 PM
BLD04-01905 FIRE-Final Inspection9/27/20049/28/20049/28/2004 12:00:00 AMPFAIL
Repair emergency lights in retail area. When this is done a temporary occupancy can be given with dave millers permission until the fire alarm is complete 9/28/2004 1:29:41 PM
BLD04-01908 FIRE-Final Inspection9/27/20049/28/20049/28/2004 12:00:00 AMPPART
Temporary occupancy is ok with dave millers permission until the fire alarm system has been installed and approved 9/28/2004 1:28:09 PM