Inspections for the day of: Wednesday, September 28, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01020 BLD-Aging Inspection9/28/20059/28/20059/30/2005 10:18:39 AM PASS
waiting on fire
FIR05-00480 INSP-Sprinkler Rough-in9/28/20059/28/20059/29/2005 11:55:35 AMPFAIL
EC25's are overspaced at southeast side branch line above where unit heater has been deleted, in three locations upright heads are directly below roof/smoke hatches, need verification of approval on changes in the mech. and electrical rooms.
BLD04-02972 FIRE-Final Inspection9/27/20059/28/20059/28/2005 3:18:38 PMPPASS
Verified annual inspection on fire sprinkler system, permit finaled.
FIR05-00301 INSP-Final Inspection9/27/20059/28/20059/28/2005 2:23:03 PMPPASS
Hood suppression system operated properly under test conditions.
BLD05-01556 FIRE-Final Inspection9/27/20059/28/20059/28/2005 10:20:40 AMAPASS
Fire life safety passed inspection.
BLD05-02356 FIRE-Final Inspection9/28/20059/28/20059/28/2005 12:00:00 AMAPASS
Fire life safety passed inspection, items on correction notice have been amended.
FIR03-00123 INSP-Final Inspection9/28/20059/28/20059/28/2005 12:00:00 AMAPASS
Additional pump flow test performed with Jim Danes of DeBest fire, 100% and 150% rated flow verified with residual pressure at 100% satisfactory.
BLD02-03091 FIRE-Final Inspection9/28/20059/28/20059/28/2005 12:00:00 AMAPASS
Pump flow test performed with Jim Danes of DeBest fire, verified satisfactory residual pressure at 100% rated flow.
FIR05-00438 INSP-Final Inspection9/28/20059/28/20059/28/2005 12:00:00 AMAPASS
Fire sprinkler permit finaled.