BLD03-01020
| BLD-Aging Inspection | 9/28/2005 | 9/28/2005 | 9/30/2005 10:18:39 AM | | PASS |
|
|
waiting on fire
|
FIR05-00480
| INSP-Sprinkler Rough-in | 9/28/2005 | 9/28/2005 | 9/29/2005 11:55:35 AM | P | FAIL |
|
|
EC25's are overspaced at southeast side branch line above where unit heater has been deleted, in three locations upright heads are directly below roof/smoke hatches, need verification of approval on changes in the mech. and electrical rooms.
|
BLD04-02972
| FIRE-Final Inspection | 9/27/2005 | 9/28/2005 | 9/28/2005 3:18:38 PM | P | PASS |
|
|
Verified annual inspection on fire sprinkler system, permit finaled.
|
FIR05-00301
| INSP-Final Inspection | 9/27/2005 | 9/28/2005 | 9/28/2005 2:23:03 PM | P | PASS |
|
|
Hood suppression system operated properly under test conditions.
|
BLD05-01556
| FIRE-Final Inspection | 9/27/2005 | 9/28/2005 | 9/28/2005 10:20:40 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD05-02356
| FIRE-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety passed inspection, items on correction notice have been amended.
|
FIR03-00123
| INSP-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 12:00:00 AM | A | PASS |
|
|
Additional pump flow test performed with Jim Danes of DeBest fire, 100% and 150% rated flow verified with residual pressure at 100% satisfactory.
|
BLD02-03091
| FIRE-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 12:00:00 AM | A | PASS |
|
|
Pump flow test performed with Jim Danes of DeBest fire, verified satisfactory residual pressure at 100% rated flow.
|
FIR05-00438
| INSP-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|