Inspections for the day of: Thursday, September 28, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03321 Final9/28/20069/28/20069/28/2006 4:56:36 PMPFAIL
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 210.62 at least 1 recpt shall be installed directly above a show window, 358.30(A) emt shall be securely fastened within 3' of box, 725.3(B) abandoned cable (TV) shall be removed(cl2,3,or pltc) 300.11(A) support wires that do not provide secure support shall not be permitted
ELE06-03435 Permanent Service9/28/20069/28/20069/28/2006 4:51:47 PMPFAIL
DAVE BRADSHAW - CALL & HE WILL MEET @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail met contr, left corr notice, nec 110.26(F)(1)(a) there shall be no foreign piping over the electrical installation equal to the width and depth 6' above the equipment, 110.2 equipment shall be acceptable only if approved, BCC 4-05-33(A)&(B) electrical equipment shall bear the listing mark of an approved testing laboratory,NOTE: corrections shall be made within 2 weeks or further action will be taken, such as removing power
ELE06-03556 Final9/28/20069/28/20069/28/2006 3:56:20 PMPPASS
john; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-03004 Rough-In Permanent Service9/28/20069/28/20069/28/2006 3:54:23 PMPPASS
butch ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ric ok, p/s u/g n ok
ELE06-03182 Electrical Rough-In9/28/20069/28/20069/28/2006 3:13:17 PMPPASS
Please call keith (###-####) or Julie (###-####) for access. Thank you.; Phone #: ###-#### Internet Inspection Request from: Adam Staigle called contr, west 1/2 ric ok
ELE06-02921 Electrical Rough-In9/28/20069/28/20069/28/2006 2:20:22 PMPPASS
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover clg, contr will leave tiles out for lv
ELE06-03224 Electrical Rough-In9/28/20069/28/20069/28/2006 1:36:02 PMPPASS
Scheduled by a contractor via Hello! on 9/28/2006 at 10:09:39 AM. Contact: ###-####. ok to cover equipotential plane
ELE06-02719 Final9/28/20069/28/20069/28/2006 1:15:25 PMPPASS
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-03220 Electrical Rough-In9/28/20069/28/20069/28/2006 12:08:23 PMPPASS
please inspect floor plugs only. thank you; Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok to cover floor recpts only
ELE06-01990 Final9/27/20069/28/20069/28/2006 9:35:18 AMAPASS
kc; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s u/g n ok
ELE06-02887 Electrical Rough-In9/27/20069/28/20069/28/2006 9:12:29 AMAPART
Scheduled by a contractor via Hello! on 9/27/2006 at 10:16:11 AM. Contact: ###-####. west side walls hard lids only ok to cover
ELE06-01586 Final9/27/20069/28/20069/28/2006 8:39:20 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty called contr to chg a/c bkr, provide drip shield over panel, ok to final