Inspections for the day of: Thursday, September 28, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00758 FIR-Aging Inspection9/28/20069/28/200610/3/2006 11:14:09 AM DONE
Notified contractor to schedule inspection.
FIR06-00393 INSP-Final Inspection9/28/20069/28/200610/2/2006 6:32:28 PMPDEFR
Inspection to be rescheduled due to time constraints.
FIR06-00683 INSP-Sprinkler Rough-in9/27/20069/28/20069/28/2006 4:16:49 PMAPART
UG supply line hydro passed, supply line is also approved for cover as the required corrections have been made.
FIR06-00711 INSP-Final Inspection9/28/20069/28/20069/28/2006 3:22:32 PMPPASS
Fire sprinkler demo per scope of work is acceptable.
BLD06-01856 FIRE-Final Inspection9/28/20069/28/20069/28/2006 3:05:41 PMPPASS
Items on c/n have been completed, inspeciton passed.
FIR06-00665 INSP-Final Inspection9/27/20069/28/20069/28/2006 2:51:53 PMAPASS
Corrections have been verified for completion, fire alarm permit finaled.
BLD06-00376 FIRE-Final Inspection9/27/20069/28/20069/28/2006 1:54:43 PMAPART
Need to install visual indicators for keyed locking doors at the main entry/exits.
BLD06-00475 FIRE-Final Inspection9/22/20069/28/20069/28/2006 1:52:55 PMAPASS
Fire life safety passed field inspection.
FIR06-00376 INSP-Final Inspection9/28/20069/28/20069/28/2006 1:52:17 PMPPASS
Corrections at fire doors are complete, fire alarm permit finaled.
FIR06-00674 INSP-Sprinkler Rough-in9/27/20069/28/20069/28/2006 11:08:19 AMAFAIL
UG fire supply line is not properly freeze protected as required.
FIR06-00319 INSP-Sprinkler Rough-in9/27/20069/28/20069/28/2006 9:57:06 AMAFAIL
Deflectors must be within 1" to 6" of the bottom of the joist for obstructed combustible construction, see fire code review notes and general notes on plan.
BLD06-01856 FIRE-Final Inspection9/27/20069/28/20069/28/2006 9:35:32 AMAFAIL
Need to provide a current certification tag for the fire extinguisher and mount along a normal path of travel as discussed, need to provide signage and visual indicator at the main entry/exit door due to keyed locking hardware.