BLD05-02394
| FIRE-Final Inspection | 9/27/2006 | 9/28/2006 | 9/28/2006 4:25:42 PM | P | PART |
|
|
A temporary occupancy was given with Dave Hanniman's permission until the two man doors on the east side of the showroom have been provided with approved door hardware.
|
FIR06-00259
| INSP-Sprinkler Rough-in/Hydro | 9/28/2006 | 9/28/2006 | 9/28/2006 4:23:47 PM | P | PASS |
|
|
Underground hydro test passed.
|
BLD06-00007
| FIRE-Final Inspection | 9/28/2006 | 9/28/2006 | 9/28/2006 2:23:52 PM | P | FAIL |
|
|
Inspection was actually for the addition to the maintenance shop. Life safety for this area only is passed. Fire sprinklers finished in this area.
|
FIR06-00526
| INSP-Sprinkler Rough-in | 9/27/2006 | 9/28/2006 | 9/28/2006 2:15:55 PM | A | PASS |
|
|
Additional area of the canopy is ok to cover. See approved plan for location.
|
FIR06-00094
| INSP-Final Inspection | 9/26/2006 | 9/28/2006 | 9/28/2006 10:30:52 AM | A | PASS |
|
|
Permit finaled
|
MIS06-00254
| FIR-Final | 9/27/2006 | 9/28/2006 | 9/28/2006 10:16:19 AM | A | FAIL |
|
|
Tag fire extinguishers, repair exit signs and emergency lights and provide the occupancy load signs per the review comments.
|
MIS06-00255
| FIR-Final | 9/27/2006 | 9/28/2006 | 9/28/2006 9:24:11 AM | A | FAIL |
|
|
Provide battery backup for the two exit signs in the dining area, repair the emergecy light in the dining area, provide panic hardware on the second exit from the dining area as per the review comments, provide "Door to remain unlocked when building is occupied" sticker at the main exit, mount the fire extinguishers so the handles do not exceed 48" from the finished floor and provide with current inspection tags, provide recertification of the hood suppression system.
|