Inspections for the day of: Friday, September 28, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03191 Electrical Rough-In9/28/20079/28/20079/28/2007 3:58:22 PMPCANC
tom Phone #: ###-#### called contractor to explain not able to go to mall in pm, and to recall for am only
ELE07-03365 Permanent Service9/28/20079/28/20079/28/2007 3:56:47 PMPNH
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs called left message, no answer, no codes, no access
ELE07-03377 Electrical Rough-In9/27/20079/28/20079/28/2007 3:53:49 PMAPASS
Jeff, 2nd floor; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls only ok to cover
ELE07-02560 Final9/28/20079/28/20079/28/2007 3:16:34 PMPNH
Scheduled by a contractor via Hello! on 9/28/2007 at 9:23:11 AM. Contact: ###-####. called, said to call when somebody there
ELE07-03379 Rough-In Permanent Service9/28/20079/28/20079/28/2007 2:46:24 PMPPASS
Mike,
Dave will be there if there is anything incorrect. Have a great weekend! Phone #: ###-#### Internet Inspection Request from: KATHY WEIL ric ok, p/s u/g n ok
ELE07-02559 Final9/28/20079/28/20079/28/2007 2:25:30 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called, ok to final
ELE07-02558 Final9/28/20079/28/20079/28/2007 2:00:31 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called, ok to final
ELE07-03371 Final9/28/20079/28/20079/28/2007 1:29:51 PMPFAIL
need inspection for IDPCO to process the power hook up rough in and perminent service thank you (behind the house shop) supose to be unlocked Phone #: ###-#### Internet Inspection Request from: Brad Baker called contractor, left corr noyice, nec 230.24(B) service conductors shall be 12' over residential driveways or no cars parked east of service, 300.4(D) edge of raceways shall be 1 1/4" from edge of framing members, BCC all make-up shall be inspected before cover
ELE07-01468 Electrical Rough-In9/28/20079/28/20079/28/2007 12:47:33 PMPFAIL
kelly Phone #: ###-#### called, left corr notice, nec 250.28(B) shall use bonding jumper in panel, 334.30 nm cable shall be stapled within 12" of panel and not on edge, 314.17(C) nm cable shall be stapled within 8" of single gang box and not stapled on edge, 300.14 at least 6" free conductor shall be provided in each box with sheathing cut to 1/4" of cable entry,250.80 metal boxes shall be grounded,250.126(1) green ground screw shall be provided
ELE07-00663 Final9/28/20079/28/20079/28/2007 10:51:17 AMPPASS
Bob, whats going on here? You finaled this months ago, did you accidentaly hit the cancel inspection button? This has been done for quite some time and I know you ok''d it I was there that day. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey inspect was done, but may have logged on to wrong permit, ok to final
ELE07-03001 Rough-In Permanent Service9/28/20079/28/20079/28/2007 10:39:59 AMAPASS
Scheduled by a contractor via Hello! on 9/28/2007 at 7:27:04 AM. Contact: ###-####. called contr, ri ok walls and hard lids, p/s u/g n ok
ELE07-03373 Rough-In Permanent Service9/27/20079/28/20079/28/2007 9:47:16 AMAPASS
dustin Phone #: ###-#### part ri for service only, wil do rest of house later, p/s o/h rec ok
ELE07-02478 Final9/27/20079/28/20079/28/2007 9:18:57 AMAPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL corrections made, ok to final, signed occupancy card
ELE07-03370 Electrical Rough-In9/27/20079/28/20079/28/2007 8:52:27 AMAPASS
mike Phone #: ###-#### ok to cover soffit
ELE07-02451 Electrical Rough-In9/27/20079/28/20079/28/2007 8:34:43 AMAPASS
Under Ground. Please Call Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to cover kitchen area u/g anop
ELE07-02547 Electrical Rough-In9/27/20079/28/20079/28/2007 8:02:30 AMAPASS
Contact is Cory. Please inspect ceiling in Apparal Areas 11 & 12 Phone #: ###-#### Internet Inspection Request from: David Bonner ok to cover ceiling areas 11 & 12 anop