Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00745 INSP-Final Inspection9/24/20099/28/20099/29/2009 12:01:52 PMPCANC
Overbooked.
FIR09-00448 INSP-Sprinkler Rough-in9/28/20099/28/20099/28/2009 3:58:37 PMPPASS
The anti-freeze system up to the northwest wall was inspected and passed except for a small combustible pocket that required protection.
FIR09-00097 INSP-Final Inspection9/25/20099/28/20099/28/2009 3:30:28 PMAFAIL
See the city approved plans for the initiating devices tested today as marked in red. The phone lines and supervision of the NAC panels were verified. One 16ga wire needs to be changed to 14ga as discussed and atrium smoke shutter sequence of operation needs to be verified since it has not been programmed per the approved drawings.
BLD09-01649 FIRE-Final Inspection9/25/20099/28/20099/28/2009 2:21:05 PMAPASS
Life safety passed.
BLD09-01650 FIRE-Final Inspection9/25/20099/28/20099/28/2009 2:02:04 PMAPASS
Fire life safety passed
BLD09-01309 FIRE-Final Inspection9/28/20099/28/20099/28/2009 12:18:59 PMPPASS
Fire life safety passed. Matt is to provide the missing sticker at the main exit. The oxygen is not on site for quantity verification. I also notified matt that the area over the offices can not be used for storage without plan review approval.