FIR11-00508
| INSP-Sprinkler Rough-in | 9/28/2011 | 9/28/2011 | 9/28/2011 4:31:39 PM | P | CANC |
|
|
overbooked
|
FIR11-00379
| INSP-Final Inspection | 9/28/2011 | 9/28/2011 | 9/28/2011 4:28:48 PM | P | FAIL |
|
|
An additional strobe is required in Office 116. Also we could not verify EOL voltage due to the panel not operating when AC power is turned off. A fire watch will be required until the panel is repaired or replaced. I spoke to Charlie with SimplexGrinnell about this and gave him the phone number to contact the fire chief.
|
BLD11-01879
| FIRE-Conference | 9/27/2011 | 9/28/2011 | 9/28/2011 2:09:35 PM | A | DONE |
|
|
I went over life safety requirements with Trudy. One smoke alarm needs to be added at the bottom of the stairs. Also per Sam exit discharge lighting and interior emergency lighting is required.
|
FIR11-00399
| INSP-Final Inspection | 9/28/2011 | 9/28/2011 | 9/28/2011 2:06:30 PM | P | FAIL |
|
|
Tamper #1 needs adjusted, could not find the inspectors test valve so the flow switch was not tested. Also need the tamper switch and manual pull stations addresses on the panel to match the map and what is reported to central station. All other items were tested. Horns did not sync but Gary fixed this while I waited.
|
FIR11-00525
| INSP-Sprinkler Rough-in | 9/26/2011 | 9/28/2011 | 9/28/2011 11:41:33 AM | A | PASS |
|
|
Rough-in passed. I noted a conference room in the southwest corner of the new space were the small room rule is being used off of two walls. I spoke to jeff about it.
|
BLD11-01844
| FIRE-Final Inspection | 9/27/2011 | 9/28/2011 | 9/28/2011 10:48:31 AM | A | FAIL |
|
|
Repair the existing exit signs and emergency lights. Also clear the access to the east exit door.
|