Inspections for the day of: Wednesday, September 28, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00508 INSP-Sprinkler Rough-in9/28/20119/28/20119/28/2011 4:31:39 PMPCANC
overbooked
FIR11-00379 INSP-Final Inspection9/28/20119/28/20119/28/2011 4:28:48 PMPFAIL
An additional strobe is required in Office 116. Also we could not verify EOL voltage due to the panel not operating when AC power is turned off. A fire watch will be required until the panel is repaired or replaced. I spoke to Charlie with SimplexGrinnell about this and gave him the phone number to contact the fire chief.
BLD11-01879 FIRE-Conference9/27/20119/28/20119/28/2011 2:09:35 PMADONE
I went over life safety requirements with Trudy. One smoke alarm needs to be added at the bottom of the stairs. Also per Sam exit discharge lighting and interior emergency lighting is required.
FIR11-00399 INSP-Final Inspection9/28/20119/28/20119/28/2011 2:06:30 PMPFAIL
Tamper #1 needs adjusted, could not find the inspectors test valve so the flow switch was not tested. Also need the tamper switch and manual pull stations addresses on the panel to match the map and what is reported to central station. All other items were tested. Horns did not sync but Gary fixed this while I waited.
FIR11-00525 INSP-Sprinkler Rough-in9/26/20119/28/20119/28/2011 11:41:33 AMAPASS
Rough-in passed. I noted a conference room in the southwest corner of the new space were the small room rule is being used off of two walls. I spoke to jeff about it.
BLD11-01844 FIRE-Final Inspection9/27/20119/28/20119/28/2011 10:48:31 AMAFAIL
Repair the existing exit signs and emergency lights. Also clear the access to the east exit door.