Inspections for the day of: Friday, September 28, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00096 FIR-Aging Inspection9/28/20129/28/201210/1/2012 9:31:46 AM NR
Forwarded information to Scott for further action.
FIR10-00429 FIR-Aging Inspection9/28/20129/28/201210/1/2012 9:31:24 AM NR
Forwarded information to Scott for further action.
BLD12-02542 FIRE-Conference9/28/20129/28/20129/28/2012 3:50:39 PMPDONE
I met Petra and the building owner and discussed hardware options on the south/rear exit door.
FIR12-00395 INSP-Sprinkler Rough-in9/28/20129/28/20129/28/2012 3:24:08 PMPPASS
Building 11, first and second floor rough-in passed and piping can be covered. Third floor can not be covered until the tenting has been modified. Areas that can not be covered are where the heat tape and associated wiring/control is located when it is installed.
BLD11-00317 FIRE-Final Inspection9/24/20129/28/20129/28/2012 3:22:00 PMPFAIL
Provide the annual inspection for the fire sprinkler system, provide single action hardware on the exit doors and intenal pass through door, repair the emergency lighting (old emergency lighting can be removed as discussed), provide sprinkler protection in the west corridor. Sprinkler pendant is located too close to wall in west restroom. Pendants appear overspaced above east cash register.
BLD12-01863 FIRE-Final Inspection9/26/20129/28/20129/28/2012 12:33:03 PMAPASS
Life safety passed
FIR12-00459 INSP-Final Inspection9/27/20129/28/20129/28/2012 11:26:07 AMAPASS
permit finaled
FIR12-00177 FIR-Aging Inspection9/28/20129/28/20129/28/2012 9:30:03 AM NR
Per Clint the project is currently suspended but might possibly start back up.