Inspections for the day of: Friday, September 28, 2012.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02472 ELE-Aging Inspection9/28/20129/28/201210/2/2012 9:45:23 AM DONE
incorrect contact number
ELE11-00169 ELE-Aging Inspection9/28/20129/28/201210/1/2012 10:10:55 AM DONE
still under construction
ELE10-01426 ELE-Aging Inspection9/28/20129/28/20129/28/2012 4:47:57 PM DONE
electrical contractor will contact homeowner for access
ELE12-02000 Final9/28/20129/28/20129/28/2012 4:41:30 PMPPASS
Mark-as early as possible please Phone #: ###-#### UL listed partition walls final ok
ELE12-02317 Final9/28/20129/28/20129/28/2012 4:03:56 PMPPASS
MIke-as LATE as possible please Phone #: ###-#### final ok
ELE12-02141 Electrical Rough-In9/28/20129/28/20129/28/2012 3:47:04 PMPPASS
Ceiling cover where walls have already been approved Phone #: ###-#### >> Inspection requested via web by Patrick D Gill rough-in ok cover ceiling grid inside yellow lines and dated
ELE12-02416 Final9/28/20129/28/20129/28/2012 3:16:12 PMPPART
Partial final for temporary occupancy ok
ELE12-02416 Electrical Rough-In9/27/20129/28/20129/28/2012 3:14:57 PMPPASS
See Temo onsite for the tour.
Please Final this permit when you are finished so they can get occupancy. If they have me do any additional work I will pull a new permit.
Thanks!!! Dan. >> Inspection requested via web by Dan Mitchell rough-in ok need to support ceiling boxes for final
ELE12-01410 Electrical Rough-In9/28/20129/28/20129/28/2012 2:38:09 PMPPASS
Contact: Clat Freinwald. 2nd floor slab inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover conduits in 2nd floor slab
ELE12-02103 Electrical Rough-In9/28/20129/28/20129/28/2012 2:21:37 PMPPASS
Grid Phone #: ###-#### >> Inspection requested via web by Dan Rohl rough-in ok cover ceiling grid 1st floor
ELE12-02412 Rough-In Permanent Service9/27/20129/28/20129/28/2012 2:03:28 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson rough-in p/s u/g n ok
ELE12-01364 Electrical Rough-In9/27/20129/28/20129/28/2012 1:27:29 PMAFAIL
Roger Phone #: ###-#### NEC 300.4(D) Maintain romex 1 1/4 from edge of framing members NEC 334.30 NM cable shall be stapled (supported) within 12 in. of device box, than every 4 1/2 feet there after
ELE10-00542 ELE-Aging Inspection9/28/20129/28/20129/28/2012 11:14:22 AM DONE
still under construction
ELE12-02235 Conference9/27/20129/28/20129/28/2012 10:55:39 AMADONE
Michael Phone #: ###-#### Discussed branch circuit for hot tub Check tub for UL listing and ok cover trench
ELE12-02237 Electrical Rough-In9/27/20129/28/20129/28/2012 9:54:52 AMAFAIL
bud Phone #: ###-#### Ceiling grid NEC300.4 (F) Cables and raceways installed in shallow grooves Possible future phsyical damage
ELE12-01818 Final9/27/20129/28/20129/28/2012 9:17:07 AMAPASS
Contact is Carl Petteck ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell final ok
ELE12-02403 Temporary Service9/26/20129/28/20129/28/2012 8:35:27 AMAPASS
THANKS, BILL Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE12-00274 Final9/27/20129/28/20129/28/2012 8:28:59 AMAFAIL
kelly Phone #: ###-#### NEC 210.8 all 125 volt single phase 15 and 20 ampere receptacles installed outdoors shall have GFCI protection. All electrical devices shall be install in UL listed enclosure. NEC 406.8(B) All 15 and 20 ampere receptacles installed in wet locations shall be listed weather resistance type. NEC 406.8(A) weatherproof receptacle cover are required
ELE12-02324 Rough-In Permanent Service9/27/20129/28/20129/27/2012 4:31:19 PMAPASS
A.M. or P.M. is fine Phone #: ###-#### >> Inspection requested via web by Joe Thomas rough-in p/s u/g n ok
ELE12-02325 Rough-In Permanent Service9/27/20129/28/20129/27/2012 4:23:30 PMAPASS
A.M. or P.M. is fine Phone #: ###-#### >> Inspection requested via web by Joe Thomas rough-in p/s u/g n ok