ELE12-01835
| ELE-Aging Inspection | 9/28/2015 | 9/28/2015 | 10/2/2015 11:09:02 AM | | DONE |
|
|
Waiting on owner
|
ELE13-01184
| ELE-Aging Inspection | 9/28/2015 | 9/28/2015 | 10/2/2015 11:02:52 AM | | DONE |
|
|
Waiting on contractor
|
ELE12-01841
| ELE-Aging Inspection | 9/28/2015 | 9/28/2015 | 9/30/2015 2:42:09 PM | | DONE |
|
|
Still under construction
|
ELE15-03088
| Rough-In Permanent Service | 9/25/2015 | 9/28/2015 | 9/28/2015 2:45:17 PM | P | PASS |
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 50 amp temp GFI not tripping asked wireman on sight to check. Rough in ok cover
|
ELE15-02800
| Rough-In Permanent Service | 9/28/2015 | 9/28/2015 | 9/28/2015 2:35:50 PM | P | CANC |
|
|
Any questions please let me know, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Been inspected prior no new work at this time.
|
ELE15-02303
| Electrical Rough-In | 9/28/2015 | 9/28/2015 | 9/28/2015 2:12:22 PM | P | PASS |
|
|
READY ANYTIME TODAY Phone #: ###-#### Inspection requested via web by mike brown Kitchen, outdoor enclosed patio rough in ok cover
|
ELE15-03101
| Rough-In Permanent Service | 9/28/2015 | 9/28/2015 | 9/28/2015 1:29:15 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 300.18- Raceway system shall be complete. riser. 300.15- A box shall be installed at each outlet point. up vanity. 334.15- NM cable shall not be installed where subject to physical damage. Top stair. 334.30- NM cable shall be secured with in 12" of a box. up vanity.
|
ELE14-01816
| Final | 9/25/2015 | 9/28/2015 | 9/28/2015 11:57:08 AM | A | PASS |
|
|
Final for occupancy for Skilled Nursing Building J Contact Brandon Keating @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
ELE15-02415
| Final | 9/25/2015 | 9/28/2015 | 9/28/2015 11:07:50 AM | A | FAIL |
|
|
Garage code 2020E Phone #: ###-#### Inspection requested via web by Alan Lusk 210.12(A)- AFCI protection shall be provided for all room with a closet with hanging rods present.
|
ELE15-02482
| Rough-In Permanent Service | 9/28/2015 | 9/28/2015 | 9/28/2015 10:19:31 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Grounding electrode system consists of ground rod, concrete encased, and underground water pipe all bonded. 600 amp 120 208 volt service. 110.24- Available fault current shall be posted with date calculated prior to service hook up.
|
ELE15-03092
| Permanent Service | 9/25/2015 | 9/28/2015 | 9/28/2015 9:54:47 AM | A | PASS |
|
|
The access code is 6180, the lock box is on the back door, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren p/s u/g rec ok
|
ELE15-03092
| Final | 9/28/2015 | 9/28/2015 | 9/28/2015 9:54:43 AM | P | PASS |
|
|
The access code is 6180, the lock box is on the back door, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Service reconnect final ok
|
ELE15-02673
| Electrical Rough-In | 9/27/2015 | 9/28/2015 | 9/28/2015 9:25:53 AM | A | PASS |
|
|
need ceiling cover or final if possible call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig Grid rough in ok cover
|
ELE15-02673
| Final | 9/28/2015 | 9/28/2015 | 9/28/2015 9:19:23 AM | P | PASS |
|
|
need ceiling cover or final if possible call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig Final ok
|
ELE15-02306
| Final | 9/25/2015 | 9/28/2015 | 9/28/2015 8:54:08 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE15-02493
| Final | 9/25/2015 | 9/28/2015 | 9/28/2015 8:33:54 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|