Inspections for the day of: Monday, September 28, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01835 ELE-Aging Inspection9/28/20159/28/201510/2/2015 11:09:02 AM DONE
Waiting on owner
ELE13-01184 ELE-Aging Inspection9/28/20159/28/201510/2/2015 11:02:52 AM DONE
Waiting on contractor
ELE12-01841 ELE-Aging Inspection9/28/20159/28/20159/30/2015 2:42:09 PM DONE
Still under construction
ELE15-03088 Rough-In Permanent Service9/25/20159/28/20159/28/2015 2:45:17 PMPPASS
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
50 amp temp GFI not tripping asked wireman on sight to check. Rough in ok cover
ELE15-02800 Rough-In Permanent Service9/28/20159/28/20159/28/2015 2:35:50 PMPCANC
Any questions please let me know, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Been inspected prior no new work at this time.
ELE15-02303 Electrical Rough-In9/28/20159/28/20159/28/2015 2:12:22 PMPPASS
READY ANYTIME TODAY Phone #: ###-#### Inspection requested via web by mike brown Kitchen, outdoor enclosed patio rough in ok cover
ELE15-03101 Rough-In Permanent Service9/28/20159/28/20159/28/2015 1:29:15 PMPFAIL
Phone #: ###-#### Inspection requested via web by Greg Traudt 300.18- Raceway system shall be complete. riser.
300.15- A box shall be installed at each outlet point. up vanity.
334.15- NM cable shall not be installed where subject to physical damage. Top stair.
334.30- NM cable shall be secured with in 12" of a box. up vanity.
ELE14-01816 Final9/25/20159/28/20159/28/2015 11:57:08 AMAPASS
Final for occupancy for Skilled Nursing Building J
Contact Brandon Keating @ ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
ELE15-02415 Final9/25/20159/28/20159/28/2015 11:07:50 AMAFAIL
Garage code 2020E Phone #: ###-#### Inspection requested via web by Alan Lusk 210.12(A)- AFCI protection shall be provided for all room with a closet with hanging rods present.
ELE15-02482 Rough-In Permanent Service9/28/20159/28/20159/28/2015 10:19:31 AMAFAIL
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Grounding electrode system consists of ground rod, concrete encased, and underground water pipe all bonded. 600 amp 120 208 volt service. 110.24- Available fault current shall be posted with date calculated prior to service hook up.
ELE15-03092 Permanent Service9/25/20159/28/20159/28/2015 9:54:47 AMAPASS
The access code is 6180, the lock box is on the back door, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren p/s u/g rec ok
ELE15-03092 Final9/28/20159/28/20159/28/2015 9:54:43 AMPPASS
The access code is 6180, the lock box is on the back door, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Service reconnect final ok
ELE15-02673 Electrical Rough-In9/27/20159/28/20159/28/2015 9:25:53 AMAPASS
need ceiling cover or final if possible call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig Grid rough in ok cover
ELE15-02673 Final9/28/20159/28/20159/28/2015 9:19:23 AMPPASS
need ceiling cover or final if possible call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig Final ok
ELE15-02306 Final9/25/20159/28/20159/28/2015 8:54:08 AMAPASS
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE15-02493 Final9/25/20159/28/20159/28/2015 8:33:54 AMAPASS
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok