Inspections for the day of: Wednesday, September 28, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01721 FIRE-Conference9/28/20169/28/20169/28/2016 4:35:16 PMPDONE
Fire conference complete, items needed for life fire safety inspection reviewed.
BLD15-01721 FIRE-Final Inspection9/27/20169/28/20169/28/2016 4:33:43 PMPCANC
Inspection request was for a fire conference, project is not ready for life fire safety final.
FIR16-00265 INSP-Sprinkler Rough-in9/27/20169/28/20169/28/2016 4:32:26 PMPPASS
24 hour air test for dry systems locared in the VRT section complete. Rough to cover inspection for all overhead fire sprinkler piping located VRT complete, all overhead fire sprinkler piping located in VRT approved for cover.
FIR16-00146 INSP-Sprinkler Rough-in/Hydro9/27/20169/28/20169/28/2016 4:30:43 PMPPASS
200 psi hydrostatic test for overhead fire sprinkler on levels 8 and 9 complete.
FIR13-00167 INSP-Sprinkler Rough-in/Hydro9/27/20169/28/20169/28/2016 4:29:56 PMPPASS
Rough in inspection for overhead fire sprinkler piping garage dry system 5 complete. 200 psi hydrostatic test for garage dry systems 5 and 7 complete
FIR16-00100 INSP-Sprinkler Rough-in/Hydro9/27/20169/28/20169/28/2016 11:52:27 AMAPART
200 psi hydrostatic test for overhead fire sprinkler piping complete. Rough in inspection for overhead fire sprinkler piping complete. 24 hour air test started at 11:00AM 28SEPT2016 with 40psi on gauge.
BLD15-02982 FIRE-Final Inspection9/28/20169/28/20169/28/2016 11:49:54 AMPPASS
Previously noted items have been repaired/addressed. No fire sprinklers, no fire alarms, fire extinguishers is in place with current inspection tag. Final life fire safey inspection passed/complete.
FIR16-00569 INSP-Sprinkler Rough-in9/28/20169/28/20169/28/2016 11:14:51 AMPPASS
Rough to cover inspection for fire sprinkler piping located above hardlids in restroom and soffits in dining area complete, overhead fire sprinkler piping in noted area's approved for cover.
BLD16-03245 FIRE-Final Inspection9/27/20169/28/20169/28/2016 10:46:02 AMACANC
Inspection request cancelled per conversation with Greg Phone #: ###-####, inspection will rescheduled for a later date.