FIR16-00285
| INSP-Sprinkler Rough-in/Hydro | 9/27/2017 | 9/28/2017 | 9/28/2017 3:29:22 PM | P | PART |
|
|
Hydrostatic test for level 1 dry system complete. 24 hour air test start at 3:00PM @ 41PSI
|
FIR16-00616
| INSP-Alarm Testing | 9/27/2017 | 9/28/2017 | 9/28/2017 1:40:13 PM | P | DONE |
|
|
Alarm testing complete for the day.
|
BLD17-00070
| FIRE-Final Inspection | 9/28/2017 | 9/28/2017 | 9/28/2017 1:39:42 PM | P | PASS |
|
|
No fire sprinkler, no fire alarms, fire extinguisher will be mounted in discussed location, all have current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00562
| INSP-Sprinkler Rough-in | 9/28/2017 | 9/28/2017 | 9/28/2017 1:21:41 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/upright heads above hardlids complete, hardlids approved for cover.
|
BLD17-02405
| FIRE-Final Inspection | 9/27/2017 | 9/28/2017 | 9/28/2017 11:26:16 AM | A | PASS |
|
|
Fire sprinkler inspection for area of work complete, fire alarm inspection for area of work complete, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
FIR16-00616
| INSP-Alarm Testing | 9/27/2017 | 9/28/2017 | 9/28/2017 11:23:37 AM | A | DONE |
|
|
Fire alarm testing complete for today, audio/visual notification complete for level 1 to include parking, level 2 parking and level 3 corridor/rooms. Stairwell pressurization to include elevator shaft pressurization complete. Room notification complete for levels 3 and 10. Visual notification will be added to the 2 balconies off of the level 3 conference room on the northwest corner.
|
FIR16-00285
| INSP-Sprinkler Rough-in/Hydro | 9/27/2017 | 9/28/2017 | 9/28/2017 11:18:27 AM | A | PART |
|
|
24 hour air test for level 2 dry system started at 7:15AM @ 40PSI
|
FIR17-00502
| INSP-Sprinkler Rough-in | 9/27/2017 | 9/28/2017 | 9/28/2017 8:40:43 AM | P | CANC |
|
|
Call Chris. Rough-In for underground feed. Phone #: ###-#### >> Inspection requested via web by Sheldon Gray Inspection cancelled from web by: Sheldon Gray
|
BLD17-02723
| FIRE-Final Inspection | 9/27/2017 | 9/28/2017 | 9/28/2017 8:37:43 AM | A | FAIL |
|
|
All exit lights/emergency lighting in tenant sapce needs serviced, provide emergency lighting for exit discharge above both south exit doors. Items on rear storage racking needs to be lowered, need 24 inches of clearance between ceiling and top of storage in non-sprinklered buildings. Provide cover plates fo open electrical boxes where wire is visible.
|