Inspections for the day of: Thursday, September 28, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00285 INSP-Sprinkler Rough-in/Hydro9/27/20179/28/20179/28/2017 3:29:22 PMPPART
Hydrostatic test for level 1 dry system complete. 24 hour air test start at 3:00PM @ 41PSI
FIR16-00616 INSP-Alarm Testing9/27/20179/28/20179/28/2017 1:40:13 PMPDONE
Alarm testing complete for the day.
BLD17-00070 FIRE-Final Inspection9/28/20179/28/20179/28/2017 1:39:42 PMPPASS
No fire sprinkler, no fire alarms, fire extinguisher will be mounted in discussed location, all have current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00562 INSP-Sprinkler Rough-in9/28/20179/28/20179/28/2017 1:21:41 PMPPART
Rough to cover inspection for overhead fire sprinkler piping/upright heads above hardlids complete, hardlids approved for cover.
BLD17-02405 FIRE-Final Inspection9/27/20179/28/20179/28/2017 11:26:16 AMAPASS
Fire sprinkler inspection for area of work complete, fire alarm inspection for area of work complete, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection for area of work passed/complete.
FIR16-00616 INSP-Alarm Testing9/27/20179/28/20179/28/2017 11:23:37 AMADONE
Fire alarm testing complete for today, audio/visual notification complete for level 1 to include parking, level 2 parking and level 3 corridor/rooms. Stairwell pressurization to include elevator shaft pressurization complete. Room notification complete for levels 3 and 10. Visual notification will be added to the 2 balconies off of the level 3 conference room on the northwest corner.
FIR16-00285 INSP-Sprinkler Rough-in/Hydro9/27/20179/28/20179/28/2017 11:18:27 AMAPART
24 hour air test for level 2 dry system started at 7:15AM @ 40PSI
FIR17-00502 INSP-Sprinkler Rough-in9/27/20179/28/20179/28/2017 8:40:43 AMPCANC
Call Chris. Rough-In for underground feed. Phone #: ###-#### >> Inspection requested via web by Sheldon Gray Inspection cancelled from web by: Sheldon Gray
BLD17-02723 FIRE-Final Inspection9/27/20179/28/20179/28/2017 8:37:43 AMAFAIL
All exit lights/emergency lighting in tenant sapce needs serviced, provide emergency lighting for exit discharge above both south exit doors. Items on rear storage racking needs to be lowered, need 24 inches of clearance between ceiling and top of storage in non-sprinklered buildings. Provide cover plates fo open electrical boxes where wire is visible.