Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00104 INSP-Alarm Testing9/29/20039/29/20039/29/2003 12:00:00 AMAPART
tested all exsisting sprinkler control tampers and flows- okay; tested new residential tampers and flows - okay; still need to verify phase reversal for fire pump
FIR03-00068 INSP-Alarm Testing9/29/20039/29/20039/29/2003 12:00:00 AMAFAIL
tested all exsisting and new tampers and flows - okay; still need to verify phase reversal; system pressure over 175 psi
MIS03-00191 FIR-Final9/26/20039/29/20039/29/2003 12:00:00 AMAPART
kevin ###-#### canopies for fire sprinklers and head overspaced by water heater in restroom area; hang extinguisher with current tag; needs emergency lighting (2 exits required) and exit signs to operate on battery power 9/29/2003 12:46:33 PM
BLD02-00090 FIRE-Final Inspection9/26/20039/29/20039/29/2003 12:00:00 AMAFAIL
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need to verify phase reversal for fire pump; wasn't a final but tested all sprinkler tampers and flows for exsisting and new systems; see previous final for correction list 9/29/2003 10:25:20 AM
BLD03-01925 FIRE-Final Inspection9/29/20039/29/20039/29/2003 12:00:00 AMPPASS
david; Phone #: ###-#### Internet Inspection Request from: Annette Moore the fire panel is scheduled for complete replacement and the plans will be submitted to the city within a few weeks; this permit is okay for occupancy 9/29/2003 1:44:36 PM
BLD03-00450 FIRE-Final Inspection9/29/20039/29/20039/29/2003 12:00:00 AMPPASS
nick; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD03-01825 FIRE-Final Inspection9/29/20039/29/20039/29/2003 12:00:00 AMPPASS
larry hansen-- ###-####--call 1st before access didn't have plans on site and I talked to Dan Stuart about the project concerning the exiting and it will work as installed 9/29/2003 3:41:19 PM
FIR03-00561 INSP-Final Inspection9/29/20039/29/20039/29/2003 12:00:00 AMPPASS