FIR04-00465
| INSP-Final Inspection | 9/28/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | A | FAIL |
|
|
rick - Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need sprinkler head in coatroom as shown on plans 9/29/2004 8:51:55 AM
|
BLD04-00847
| FIRE-Final Inspection | 9/28/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | A | FAIL |
|
|
rick - Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Remove arrow on exit sign at main exit; post occupant load sign; deadbolts on media rooma nd electrical room must release from inside; complete sprinklers in coat room 9/29/2004 11:12:41 AM
|
BLD04-01408
| FIRE-Final Inspection | 9/28/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | A | PASS |
|
|
gil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD03-02187
| FIRE-Conference | 9/28/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | A | PART |
|
|
TIM WILL CALL ABOUT CONFERENCE; Phone #: ###-#### Internet Inspection Request from: Linda Hartwell The owner wants to sprinkler the TI spaces and not the brew pub; per conversation with Ron Hill the plans were submitted with the building being fully sprinklered; per Ron the architect will have to submit showing the building not sprinklered; left message with Tim about this requirement 9/29/2004 10:34:05 AM
|
FIR04-00435
| INSP-Final Inspection | 9/29/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | PASS |
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIR03-00810
| INSP-Alarm Testing | 9/29/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | PASS |
|
|
Cell Phone ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino Wall layout has changed and the strobes were modified to ceiling mount with 75 and 30 candela in new rooms 9/29/2004 1:55:12 PM
|
FIR04-00441
| INSP-Final Inspection | 9/29/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | FAIL |
|
|
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino SR and QR heads mixed in same fire area 9/29/2004 2:09:09 PM
|
BLD04-01319
| FIRE-Final Inspection | 9/29/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/29/2004 at 9:06:43 AM. Contact: ###-####. Need to complete sprinkler permit 9/29/2004 2:09:44 PM
|
FIR04-00429
| INSP-Sprinkler Rough-in/Hydro | 9/29/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/29/2004 at 10:59:04 AM. Contact: ###-####.
|
BLD04-01070
| FIRE-Final Inspection | 9/29/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | PASS |
|
|
|
FIR03-00690
| INSP-Final Inspection | 9/27/2004 | 9/29/2004 | 9/29/2004 12:00:00 AM | P | FAIL |
|
|
as late as possible please///clifford; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Room sounder base detectors are not temporal tone on general alarm; strobes not sync'd; EOL voltage drop 20.5 on 6th floor circuit - all others are okay; need maps; mount remote annunciator permanently 9/30/2004 9:12:25 AM
|