Inspections for the day of: Wednesday, September 29, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00465 INSP-Final Inspection9/28/20049/29/20049/29/2004 12:00:00 AMAFAIL
rick - Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need sprinkler head in coatroom as shown on plans 9/29/2004 8:51:55 AM
BLD04-00847 FIRE-Final Inspection9/28/20049/29/20049/29/2004 12:00:00 AMAFAIL
rick - Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Remove arrow on exit sign at main exit; post occupant load sign; deadbolts on media rooma nd electrical room must release from inside; complete sprinklers in coat room 9/29/2004 11:12:41 AM
BLD04-01408 FIRE-Final Inspection9/28/20049/29/20049/29/2004 12:00:00 AMAPASS
gil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD03-02187 FIRE-Conference9/28/20049/29/20049/29/2004 12:00:00 AMAPART
TIM WILL CALL ABOUT CONFERENCE; Phone #: ###-#### Internet Inspection Request from: Linda Hartwell The owner wants to sprinkler the TI spaces and not the brew pub; per conversation with Ron Hill the plans were submitted with the building being fully sprinklered; per Ron the architect will have to submit showing the building not sprinklered; left message with Tim about this requirement 9/29/2004 10:34:05 AM
FIR04-00435 INSP-Final Inspection9/29/20049/29/20049/29/2004 12:00:00 AMPPASS
eric; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR03-00810 INSP-Alarm Testing9/29/20049/29/20049/29/2004 12:00:00 AMPPASS
Cell Phone ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino Wall layout has changed and the strobes were modified to ceiling mount with 75 and 30 candela in new rooms 9/29/2004 1:55:12 PM
FIR04-00441 INSP-Final Inspection9/29/20049/29/20049/29/2004 12:00:00 AMPFAIL
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino SR and QR heads mixed in same fire area 9/29/2004 2:09:09 PM
BLD04-01319 FIRE-Final Inspection9/29/20049/29/20049/29/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 9/29/2004 at 9:06:43 AM. Contact: ###-####. Need to complete sprinkler permit 9/29/2004 2:09:44 PM
FIR04-00429 INSP-Sprinkler Rough-in/Hydro9/29/20049/29/20049/29/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/29/2004 at 10:59:04 AM. Contact: ###-####.
BLD04-01070 FIRE-Final Inspection9/29/20049/29/20049/29/2004 12:00:00 AMPPASS
FIR03-00690 INSP-Final Inspection9/27/20049/29/20049/29/2004 12:00:00 AMPFAIL
as late as possible please///clifford; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Room sounder base detectors are not temporal tone on general alarm; strobes not sync'd; EOL voltage drop 20.5 on 6th floor circuit - all others are okay; need maps; mount remote annunciator permanently 9/30/2004 9:12:25 AM