Inspections for the day of: Wednesday, September 29, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00505 INSP-Final Inspection9/28/20049/29/20049/29/2004 12:00:00 AMAFAIL
Upright sprinkler heads which are spaced too far off of the exterior wall in the cavity have not been addressed. Small room rule can not be used. See nfpa 13; 3.3.20 for definition of a small room. Must have walls and a ceiling. Reinspection fee for fourth inspection for same item applied. 9/29/2004 10:06:46 AM
FIR04-00581 INSP-Final Inspection9/28/20049/29/20049/29/2004 12:00:00 AMAFAIL
Insulation is falling from the deck onto the sprinkler piping and uprights. Provide clearance per NFPA 13 9/29/2004 11:05:20 AM
FIR04-00463 INSP-Sprinkler Rough-in/Hydro9/28/20049/29/20049/29/2004 12:00:00 AMAFAIL
Overhead sprinkler piping was inspected. Offices, riser and FDC not inspected. I found many sprinkler uprights covered with tape, one upright bent, earthquake bracing was missing and retaining straps missing from one side of the trapeze hangers. See approved plans for specific locations. Underground flush was ok and entry was made under FIR04-00384. 9/29/2004 11:10:41 AM
BLD04-00656 FIRE-Final Inspection9/28/20049/29/20049/29/2004 12:00:00 AMAPASS
Fire life safety finaled 9/29/2004 12:32:54 PM
BLD04-01819 FIRE-Sprinkler Rough-in9/29/20049/29/20049/29/2004 12:00:00 AMPFAIL
I spoke to Dave Miller and he has not heard back from Teresa about approval of the bond so no inspection was performed. Per Dave all life safety items will need to be complete prior to any temporyary occupancy being given. This was passed on to Dennis with HC. 9/29/2004 3:03:06 PM
FIR04-00384 INSP-Sprinkler Rough-in/Hydro9/29/20049/29/20049/29/2004 12:00:00 AMPCANC
BLD04-01672 FIRE-Final Inspection9/29/20049/29/20049/29/2004 12:00:00 AMPFAIL
Fire sprinkler permit needs finaled. Provide approved door hardware to storage room and provide verification of duct detector testing or test detector 9/29/2004 4:05:43 PM
FIR04-00384 INSP-Supply line flush9/29/20049/29/20049/29/2004 12:00:00 AMPPASS
underground supply line flush is ok 9/29/2004 2:12:18 PM
BLD04-00657 FIRE-Final Inspection9/29/20049/29/20049/29/2004 12:00:00 AMPPASS
fire life safety finaled