Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02458 ELE-Aging Inspection9/29/20069/29/200610/2/2006 1:37:46 PM CANC
ELE06-03551 Final9/29/20069/29/20069/29/2006 4:02:13 PMPFAIL
Jason; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
called not ready for final needs r/i shall remove all devices, and remove sheet rock patches so I can inspect, and wire kitchen to current code requirements
ELE06-03185 Electrical Rough-In9/29/20069/29/20069/29/2006 3:36:33 PMPPART
need rough in on new building. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. posted for damaged wiring done by concrete contr, shall repair or turn off power, called contr . will address problem, r/i for ceilings ok
ELE06-02216 Final9/29/20069/29/20069/29/2006 3:03:29 PMPPASS
Scheduled by a contractor via Hello! on 9/29/2006 at 7:40:39 AM. Contact: ###-####. ok
ELE06-03622 Temporary Service9/29/20069/29/20069/29/2006 1:39:55 PMPPASS
Phone #: ###-#### Internet Inspection Request from: TJ Sturges t/s o/h new ok
ELE06-03616 Final9/29/20069/29/20069/29/2006 1:39:36 PMPPASS
DAVE BRADSHAW - CALL & HE WILL MEET @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail
ELE06-03568 Electrical Rough-In9/28/20069/29/20069/29/2006 11:52:23 AMAPASS
Electrician will not be there -- homeowner will be home. Any questions, you will have to contact the shop. Thank you.; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok survey posted called box fill and remove e strip from cutin box left of range
ELE06-03503 Rough-In Permanent Service9/27/20069/29/20069/29/2006 10:58:45 AMAFAIL
Scheduled by a contractor via Hello! on 9/27/2006 at 3:58:09 PM. Contact: ###-####. corr. called 300.4(A)(1)&(D) nail plates and 11/4" parallel to studs, u/g for post light covered before inspection
ELE06-03504 Rough-In Permanent Service9/27/20069/29/20069/29/2006 10:56:27 AMAFAIL
Scheduled by a contractor via Hello! on 9/27/2006 at 3:56:43 PM. Contact: ###-####. corr. called 300.4(A)(1) nail plates ,110.14(A) lug at bond bushing loose, u/g for post light covered before inspection
ELE06-02364 Electrical Rough-In9/28/20069/29/20069/29/2006 9:56:53 AMAPART
Scheduled by a contractor via Hello! on 9/28/2006 at 5:14:26 PM. Contact: ###-####. west end exercise and spinning rms, common wall, east end exercise and corridor walls ok
ELE06-02426 Electrical Rough-In9/28/20069/29/20069/29/2006 9:25:33 AMAFAIL
Reinspect trench; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot u/g shall be 24" in parking lot, also need to know what grade is called told contr,
ELE05-04208 ELE-Aging Inspection9/29/20069/29/20069/29/2006 7:15:29 AM CANC
ELE05-04093 ELE-Aging Inspection9/29/20069/29/20069/29/2006 7:15:13 AM PART
r/i ok
ELE06-01560 Electrical Rough-In9/28/20069/29/20069/29/2006 12:00:00 AMPCANC
jeff ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley per Jim S. this permit needs to be voided see comments///dld