Inspections for the day of: Friday, September 29, 2006.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03206 Permanent Service9/29/20069/29/20069/29/2006 4:12:12 PMPPASS
Stu, ceiling inspection as well, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s exst meter pak n ok
ELE06-03554 Permanent Service9/29/20069/29/20069/29/2006 4:05:54 PMPPASS
Stu; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s exst meter pak, n ok
ELE06-03651 Permanent Service9/29/20069/29/20069/29/2006 3:20:03 PMPNR
paula; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley talked to contr, found more damage, will call next week
ELE06-02290 Final9/29/20069/29/20069/29/2006 3:12:49 PMPPASS
ted; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr about recpts , strap riser, ok to final
ELE06-03223 Final9/28/20069/29/20069/29/2006 2:49:53 PMPPASS
trent; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover clg, ok to final, no card to sign
ELE05-03058 Electrical Rough-In9/29/20069/29/20069/29/2006 2:00:40 PMPPASS
JIM WEST; Phone #: ###-#### Internet Inspection Request from: Darla Downs Please call 1/2 hr before going out . ric ok
ELE06-03489 Electrical Rough-In9/29/20069/29/20069/29/2006 1:40:09 PMPPASS
jerod ; Phone #: ###-#### Note: sheetrockers will be mon morning Internet Inspection Request from: Cathy Chiles soffits ok to cover
ELE06-03648 Conference9/29/20069/29/20069/29/2006 1:13:32 PMPDONE
casey ###-#### talked about box fill, being open to see studs, free conductor length, make-up
ELE06-03260 Electrical Rough-In9/29/20069/29/20069/29/2006 11:45:12 AMPPASS
jason Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceiling
ELE06-03251 Electrical Rough-In9/29/20069/29/20069/29/2006 11:40:43 AMPPASS
ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ceiling ok to cover
ELE06-00116 Final9/28/20069/29/20069/29/2006 10:36:02 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, equipment labelled, ok to final, signed card
ELE06-03321 Final9/28/20069/29/20069/29/2006 10:11:38 AMAPASS
john; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ok to final, signed card
ELE06-03590 Electrical Rough-In9/28/20069/29/20069/29/2006 9:59:00 AMAPASS
kathy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok
ELE06-03632 Electrical Rough-In9/28/20069/29/20069/29/2006 9:48:47 AMAPASS
wire floor heat, call Dan if needed; Phone #: ###-#### Internet Inspection Request from: Dan Rohl called ok to cover floor heat
ELE06-03620 Permanent Service9/28/20069/29/20069/29/2006 9:43:37 AMAFAIL
Meter D.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs called left corr notice, 400.5(A) #4seow cord ampacity 70a, shall not use 100a breaker for overcurrent protection,408.4 circuit directory shall be provided, 110.21 sufficient marking shall be provided on panel to identify use,NOTE: shall supply portable trailer with 100a service
ELE06-03057 Final9/28/20069/29/20069/29/2006 8:54:40 AMAPASS
Brian; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr about loose recpt and tv wire removal, ok to final, signed card
ELE06-03275 Electrical Rough-In9/28/20069/29/20069/29/2006 8:44:55 AMAPART
Scheduled by a contractor via Hello! on 9/28/2006 at 2:13:08 PM. Contact: ###-####. ok to pour gec, u/g ok to pour
ELE06-02254 Electrical Rough-In9/28/20069/29/20069/29/2006 8:15:14 AMAPART
Scheduled by a contractor via Hello! on 9/28/2006 at 2:09:04 PM. Contact: ###-####. ok to cover gec
ELE06-03224 Electrical Rough-In9/28/20069/29/20069/28/2006 10:14:57 AMACANC
equipotential grid; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack Disp set to [CANC] by a contractor via Hello! on Sep 28 2006 10:14AM.