FIR05-00805
| FIR-Aging Inspection | 9/29/2006 | 9/29/2006 | 10/3/2006 11:14:37 AM | | DEFR |
|
|
|
FIR06-00642
| INSP-Final Inspection | 9/28/2006 | 9/29/2006 | 10/2/2006 6:57:38 AM | A | DEFR |
|
|
Inspection rescheduled for 10/2.
|
BLD06-00830
| FIRE-Final Inspection | 9/29/2006 | 9/29/2006 | 9/29/2006 4:58:26 PM | P | CANC |
|
|
Not ready per conversation with contractor, inspection mistakenly scheduled.
|
FIR06-00449
| INSP-Sprinkler Rough-in/Hydro | 9/28/2006 | 9/29/2006 | 9/29/2006 4:55:15 PM | P | PART |
|
|
OH hydro and rough-in inspection for the antifreeze system at the front canopy as marked on plans are acceptable pending two heads at the north overbuild which need to be raised and three heads at the front canopy are partially blocked by an adjacent soffit.
|
FIR04-00673
| INSP-Alarm Testing | 9/28/2006 | 9/29/2006 | 9/29/2006 4:48:10 PM | P | PART |
|
|
Smoke detectors in apt. 814 and 814 1/2 tested satisfactory.
|
FIR06-00563
| INSP-Final Inspection | 9/29/2006 | 9/29/2006 | 9/29/2006 1:05:55 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-01746
| FIRE-Final Inspection | 9/28/2006 | 9/29/2006 | 9/29/2006 1:05:11 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR06-00682
| INSP-Final Inspection | 9/28/2006 | 9/29/2006 | 9/29/2006 1:04:40 PM | A | PASS |
|
|
Field adjustments and corrections have been made, final inspection passed.
|
FIR06-00598
| INSP-Final Inspection | 9/28/2006 | 9/29/2006 | 9/29/2006 1:03:33 PM | A | PASS |
|
|
Fire sprinkler permit finaled, inspection passed.
|
BLD06-01743
| FIRE-Final Inspection | 9/28/2006 | 9/29/2006 | 9/29/2006 11:57:15 AM | A | PASS |
|
|
Fire life safety is satisfactory, door hardware verified for type to be installed at missing doors.
|
FIR06-00670
| INSP-Final Inspection | 9/29/2006 | 9/29/2006 | 9/29/2006 11:55:13 AM | P | PASS |
|
|
Fire sprinkler passed final inspection.
|