Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC07-00911 Aging Inspection9/29/20099/29/20099/30/2009 8:12:39 AM CANC
ELE09-01125 ELE-Aging Inspection9/29/20099/29/20099/29/2009 3:50:25 PM CANC
ELE09-01125 Final9/29/20099/29/20099/29/2009 3:50:20 PMPPASS
ok survey for handhole at pole
ELE09-01027 Final9/28/20099/29/20099/29/2009 3:01:10 PMPNH
Zane Phone #: ###-#### notice posted called no access
ELE09-01756 Electrical Rough-In9/29/20099/29/20099/29/2009 2:29:50 PMPFAIL
bud Phone #: ###-#### met contr 300.11 needs support wirs for high and low volt cables, shall not use ceiling or fixture support wires, secure mc within 12" of boxes, needs bushings for conduits for low volt cables
ELE09-01466 Electrical Rough-In9/28/20099/29/20099/29/2009 1:24:02 PMPFAIL
Exterior underground Phone #: ###-#### Internet Inspection Request from: BARRY KENDALL needs proper depth for conduits in parkinglot, also need grade shot for reference points to inspect
ELE09-01356 Final9/28/20099/29/20099/29/2009 12:20:34 PMPPASS
Brian ###-#### p/o ok card signed
ELE09-01846 Electrical Rough-In9/28/20099/29/20099/29/2009 12:20:09 PMAPASS
Brian ###-#### walls ok
ELE09-01786 Permanent Service9/28/20099/29/20099/29/2009 9:41:35 AMAFAIL
warren - please call 1/2 hr prior so he can meet you there Phone #: ###-#### met contr, needs support for all 3 mast, conn. where cables enter cabinets, 260.52(A)(1) grd u/g water within 5ft of where it first enters, use sun res. wire in mast, all conductors of circuits shall be same size, 225.30 thru 225.36 needs p/s for out building see 250.32 for grding at out building note no romex in outside conduits, wire not suited for wet location , no violation retained address sub panel at garage also no cord for welder recept, if ? call me
ELE09-01841 Electrical Rough-In9/28/20099/29/20099/29/2009 8:55:41 AMAPASS
Underground conduit inspection Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called bed u/g in sand or gravel ok
ELE09-01109 Electrical Rough-In9/29/20099/29/20099/29/2009 8:19:16 AMAPART
waiting for wall sign
ELE09-01808 Electrical Rough-In9/28/20099/29/20099/29/2009 8:18:22 AMAPASS
###-#### Internet Inspection Request from: Todd Holbrook walls ok