Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00745 INSP-Final Inspection9/29/20099/29/20099/29/2009 4:13:48 PMPPASS
Permit finaled
FIR09-00097 INSP-Final Inspection9/28/20099/29/20099/29/2009 3:15:46 PMAFAIL
The inspection continued today. Items left to test include the hood suppression system, hvac shutdown, EOL voltage drop, smoke alarms, smoke shutters/atrium smoke detectors and sprinkler system interconnections. Notification and initiating (smoke detectors/pull stations) were tested on all floors. Two were repaired while I waited.
FIR09-00448 INSP-Sprinkler Rough-in/Hydro9/28/20099/29/20099/29/2009 2:27:18 PMAPASS
The rough-in for the anti-freeze system and the wet system passed. Two uprights had to be added to cover two overbuild areas. Piping can not be covered due to the tenting being incomplete in many areas. The riser has not been built yet.