BLD09-00832
| FIRE-Conference | 9/22/2011 | 9/29/2011 | 9/30/2011 11:28:25 AM | A | DONE |
|
|
Follow up on permit status with John blake ###-#### or jerry ###-####
|
BLD11-00406
| FIRE-Conference | 9/29/2011 | 9/29/2011 | 9/29/2011 3:48:08 PM | P | DONE |
|
|
While performing a sprinkler inspection I noticed that the exterior door hardware does not meet chapter 10 of the IBC and IFC. I spoke to shane about options. It also does not appear that exit discharge lighting has been installed as required per the building plan review comments.
|
FIR11-00262
| INSP-Final Inspection | 9/29/2011 | 9/29/2011 | 9/29/2011 3:44:26 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00023
| INSP-Sprinkler Rough-in | 9/29/2011 | 9/29/2011 | 9/29/2011 2:48:31 PM | P | PASS |
|
|
The remaining sprinkler piping is ok to cover
|
FIR11-00469
| INSP-Sprinkler Rough-in | 9/29/2011 | 9/29/2011 | 9/29/2011 2:42:59 PM | P | PASS |
|
|
Sprinkler piping is ok to cover in restrooms marked "ok" with todays date.
|
FIR11-00498
| INSP-Final Inspection | 9/28/2011 | 9/29/2011 | 9/29/2011 1:21:11 PM | A | PASS |
|
|
Permit finaled. The bulbs and the wiring have been removed from the lights under the hood.
|
BLD11-02295
| FIRE-Final Inspection | 9/29/2011 | 9/29/2011 | 9/29/2011 1:17:38 PM | P | PASS |
|
|
life safety passed
|
FIR11-00473
| INSP-Sprinkler Rough-in | 9/28/2011 | 9/29/2011 | 9/29/2011 1:15:40 PM | A | PASS |
|
|
The entry area soffit sprinkler piping is ok to cover. I noted on the city approved plans where coverage is blocked by a header directly above/at the entry door.
|
BLD11-02295
| FIRE-Final Inspection | 9/28/2011 | 9/29/2011 | 9/29/2011 10:04:26 AM | A | FAIL |
|
|
Repair the south emergency light. All other items are ok.
|
BLD11-00894
| FIRE-Final Inspection | 9/27/2011 | 9/29/2011 | 9/29/2011 9:07:10 AM | A | PASS |
|
|
Life safety passed. The maintenance chief and I spoke about the importance of getting the annual testing performed on the building fire alarm system.
|
FIR11-00389
| INSP-Final Inspection | 9/28/2011 | 9/29/2011 | 9/29/2011 9:05:31 AM | A | PASS |
|
|
permit finaled
|