Inspections for the day of: Tuesday, September 29, 2015.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Little
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM15-03283 Plumbing Rough-in9/29/20159/29/20159/29/2015 3:52:33 PMPFAIL
JOB # 18202. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
>items not corrected
PLM15-00729 PLM-Aging Inspection9/29/20159/29/20159/29/2015 3:28:31 PM FAIL
contractor has not rescheduled.
PLM15-02877 Plumbing Rough-in9/28/20159/29/20159/29/2015 3:28:01 PMPPASS
JOB # 18145. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
PLM15-03230 Plumbing Rough-in9/28/20159/29/20159/29/2015 3:27:45 PMPFAIL
JOB # 18190. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
>>hang abs every 4' in crawl
>>ok to pull test
PLM15-03231 Plumbing Rough-in9/28/20159/29/20159/29/2015 3:26:58 PMPFAIL
JOB # 18191. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
>Support trap arm lower left.
>ok to pull test
PLM15-03066 Plumbing Rough-in9/28/20159/29/20159/29/2015 3:26:00 PMPFAIL
JOB # 18171. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
>dwv test failed L. side
>ok to pull test R. side
PLM15-03336 Final9/28/20159/29/20159/29/2015 2:43:49 PMPCANC
Ruben Phone #: ###-####
PLM15-03183 Water and/or Sewer9/28/20159/29/20159/29/2015 2:26:36 PMPPART
Dan Phone #: ###-####
>both waters ok
>sewer ok up to incp.
>sewer from bldg to be replaced to existing abs.
PLM14-03117 Final9/29/20159/29/20159/29/2015 2:03:37 PMPPART
Mait Phone #: ###-#### Inspection requested via web by j mait downer jr
>need to add rps to water feeding office portion of warehouse.
>caulk sinks
PLM15-02873 Plumbing Rough-in9/28/20159/29/20159/29/2015 1:24:40 PMPPASS
JOB # 13271. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
PLM15-02875 Plumbing Rough-in9/28/20159/29/20159/29/2015 1:24:05 PMPPASS
JOB # 13300. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
PLM15-02597 Final9/28/20159/29/20159/29/2015 12:10:03 PMPPASS
Inspection requested via web by Jeffrey Hankins
PLM15-03215 Final9/24/20159/29/20159/29/2015 11:53:45 AMPPASS
Derek will give you a call when ready for inspection. Phone #: ###-#### Inspection requested via web by James Staley
PLM15-03281 Final9/28/20159/29/20159/29/2015 11:36:25 AMAPASS
Roy Phone #: ###-####
PLM15-01371 Plumbing Rough-in9/28/20159/29/20159/29/2015 11:02:05 AMAPART
DAVID IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
>Non Potable water rough in ok,
PLM15-03321 Final9/28/20159/29/20159/29/2015 10:36:32 AMAPASS
Please call Christy ###-#### when on way Phone #: ###-#### Inspection requested via web by Ben Davis
PLM15-03277 Final9/28/20159/29/20159/29/2015 10:25:56 AMAPASS
Jeff will give you a call when ready for inspection. Phone #: ###-#### Inspection requested via web by James Staley
>added ext water line to permit for new service from meter to house.
PLM15-01933 Water and/or Sewer9/28/20159/29/20159/29/2015 10:00:00 AMAFAIL
JD Phone #: ###-####
>leak at 8" wye
>uncover joints on 4" and 8"
>change c/o from 8" to 6" at 8x6 reducer.f
PLM15-03283 Plumbing Rough-in9/28/20159/29/20159/29/2015 8:43:50 AMAFAIL
JOB # 18202 Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
>DWV test failed, several leaks
>906.2-vent shall terminate no less than 10' from openable window.
>Table 3-2- provide support @ base and each floor of ABS (1.5 vent to platform drain needs supported)
PLM15-03230 Water and/or Sewer9/28/20159/29/20159/28/2015 7:05:38 PMPCANC
JOB # 18190. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes Inspection cancelled from web by: Ann Marie Reyes
PLM15-03321 Water and/or Sewer9/28/20159/29/20159/28/2015 1:28:51 PMACANC
Please call Christy ###-#### when on way Phone #: ###-#### >> Inspection requested via web by Ben Davis Inspection cancelled from web by: Ben Davis