Inspections for the day of: Thursday, September 29, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01984 ELE-Aging Inspection9/29/20169/29/20169/30/2016 2:27:15 PM PASS
Waiting on contractor
ELE16-01946 Electrical Rough-In9/29/20169/29/20169/29/2016 4:19:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Small area 1 sided with drywall prior to inspection told this is your 1 allowed. Future cover prior to inspection will be red tagged for removal.
Areas noted on contractor print walls and bath foyer wall and hardlid rough in ok cover
ELE16-01946 Conference9/29/20169/29/20169/29/2016 4:19:11 PMPDONE
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed the installation requirements for service entrance conductors to run down the outside of a building than enter an exterior wall directly into a listed fire pump controller on interior of fire pump room. 695.6(A)(1)- Service conductors for fire pump shall be physically routed outside and building and shall be installed as service entrance conductors in accordance with 230.6. Asked contractor to discuss with fire marshal if protection from traffic is needed with outside conduit is to run on outside of wall in alley behind building.
ELE13-01291 Electrical Rough-In9/29/20169/29/20169/29/2016 2:15:00 PMAPASS
site underground. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson
Area between HQ and Annex underground and south pole bases rough in ok cover
ELE16-02091 Final9/28/20169/29/20169/29/2016 10:45:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Nurse core A, B, and C completed with office furnishings. Listing and install ok.
Final ok
ELE16-03135 Electrical Rough-In9/29/20169/29/20169/29/2016 10:32:20 AMPPASS
Phone #: ###-#### Inspection requested via web by Kyle Lott
Wall rough in ok cover
ELE16-02835 Final9/28/20169/29/20169/29/2016 9:43:30 AMAPASS
Phone #: ###-#### Inspection requested via web by kendall bender
Final ok
ELE14-03316 Electrical Rough-In9/29/20169/29/20169/29/2016 8:24:06 AMPPASS
Stair SF-03 and 1ST3 walls. Electrical relocated area noted wall rough in ok cover