ELE12-01984
| ELE-Aging Inspection | 9/29/2016 | 9/29/2016 | 9/30/2016 2:27:15 PM | | PASS |
|
|
Waiting on contractor
|
ELE16-01946
| Electrical Rough-In | 9/29/2016 | 9/29/2016 | 9/29/2016 4:19:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Small area 1 sided with drywall prior to inspection told this is your 1 allowed. Future cover prior to inspection will be red tagged for removal. Areas noted on contractor print walls and bath foyer wall and hardlid rough in ok cover
|
ELE16-01946
| Conference | 9/29/2016 | 9/29/2016 | 9/29/2016 4:19:11 PM | P | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed the installation requirements for service entrance conductors to run down the outside of a building than enter an exterior wall directly into a listed fire pump controller on interior of fire pump room. 695.6(A)(1)- Service conductors for fire pump shall be physically routed outside and building and shall be installed as service entrance conductors in accordance with 230.6. Asked contractor to discuss with fire marshal if protection from traffic is needed with outside conduit is to run on outside of wall in alley behind building.
|
ELE13-01291
| Electrical Rough-In | 9/29/2016 | 9/29/2016 | 9/29/2016 2:15:00 PM | A | PASS |
|
|
site underground. Call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Area between HQ and Annex underground and south pole bases rough in ok cover
|
ELE16-02091
| Final | 9/28/2016 | 9/29/2016 | 9/29/2016 10:45:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Nurse core A, B, and C completed with office furnishings. Listing and install ok. Final ok
|
ELE16-03135
| Electrical Rough-In | 9/29/2016 | 9/29/2016 | 9/29/2016 10:32:20 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kyle Lott Wall rough in ok cover
|
ELE16-02835
| Final | 9/28/2016 | 9/29/2016 | 9/29/2016 9:43:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
ELE14-03316
| Electrical Rough-In | 9/29/2016 | 9/29/2016 | 9/29/2016 8:24:06 AM | P | PASS |
|
|
Stair SF-03 and 1ST3 walls. Electrical relocated area noted wall rough in ok cover
|