FIR16-00502
| INSP-Sprinkler Rough-in | 9/29/2016 | 9/29/2016 | 9/29/2016 2:58:42 PM | P | FAIL |
|
|
Todays inspection was for the underground supply piping. It failed because the dept. of cover does not meet the minum dept of 4'-6". It is running right around 4'-0"
|
FIR16-00427
| INSP-Final Inspection | 9/29/2016 | 9/29/2016 | 9/29/2016 2:53:50 PM | P | FAIL |
|
|
The 2" poly piping needs to be attached to the bottom of the trusses, need the city approved plans to verify the riser layout and sizing, need the flow switch/bell repaired. I spoke to the owner(husband) about the need for more fill dirt over the underground per the agreement with the fire sprinkler contractor and builder.
|
BLD16-01507
| FIRE-Final Inspection | 9/28/2016 | 9/29/2016 | 9/29/2016 11:51:39 AM | A | FAIL |
|
|
No city approved plans or notes on site. Fire extinguishers need annual inspection tag, Door hardware, exit signs, emergnecy lights and exit discharge lights worked. Fire alarm permit is finaled.
|
FIR16-00360
| INSP-Final Inspection | 9/28/2016 | 9/29/2016 | 9/29/2016 11:49:03 AM | A | PASS |
|
|
Permit finaled
|
GRD16-00043
| FIRE-Final Inspection | 9/28/2016 | 9/29/2016 | 9/29/2016 10:52:09 AM | A | PASS |
|
|
?Life safety passed. Scott Arellano approved the traffic calming devices and the less than 20' clearance at the west side of the school. I could not contact the contractor due to wrong number posted. Scott provided plans via email. Steve Phone #: ###-####
|
FIR16-00597
| INSP-Final Inspection | 9/28/2016 | 9/29/2016 | 9/29/2016 10:32:30 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00434
| INSP-Sprinkler Rough-in | 9/28/2016 | 9/29/2016 | 9/29/2016 9:06:38 AM | A | PASS |
|
|
Tenting re-inspection passed. Piping can be covered.
|
BLD16-02711
| FIRE-Final Inspection | 9/28/2016 | 9/29/2016 | 9/29/2016 9:03:07 AM | A | PASS |
|
|
life safety passed
|
BLD14-03071
| FIRE-Final Inspection | 9/28/2016 | 9/29/2016 | 9/29/2016 8:18:13 AM | A | PASS |
|
|
Life safety passed. Today I inspected units 105, 106, 205, 206, 305, 306
|