Inspections for the day of: Thursday, September 29, 2016.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01721 FIRE-Final Inspection9/29/20169/29/20169/29/2016 5:24:23 PMPPART
Partial final life fire safety inspection complete, fire sprinklers are complete with exception to various escutcheons, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags.
FIR16-00265 INSP-Sprinkler Rough-in9/27/20169/29/20169/29/2016 5:22:39 PMPPASS
200 psi hydrostatic test for VRT Dry Systems passed/complete.
FIR13-00167 INSP-Sprinkler Rough-in/Hydro9/28/20169/29/20169/29/2016 1:56:06 PMPPASS
Hydrostatic test complete for Dry system 6 and eastside hose valve system.
FIR15-00602 INSP-Sprinkler Rough-in/Hydro9/28/20169/29/20169/29/2016 1:55:11 PMPCANC
Level 1 not ready for hydrostatic test, hydro will be rescheduled for another day.
BLD16-02956 FIRE-Final Inspection9/28/20169/29/20169/29/2016 12:59:35 PMAPASS
No fire sprinklers, no fire alarms, commercial hood fire suppression system inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00614 INSP-Final Inspection9/28/20169/29/20169/29/2016 12:56:31 PMPPASS
Final commercial hood fire suppression system inspection complete.
BLD16-01124 FIRE-Final Inspection9/28/20169/29/20169/29/2016 12:30:39 PMAPART
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags, correct signage is in place. Patial final for life fire safety inspection complete, life safety can be signed off as complete after fire department inspection has been completed and passed.
FIR16-00565 INSP-Sprinkler Rough-in9/29/20169/29/20169/29/2016 11:30:43 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, previously noted noted have been addressed/repaired. Fireplace framing does not go all the way to the ceiling, discussed this with Tim Frost due to tthe approved drawings showing a head in the gas fireplace enclosure, due to this application Tim is okay with the head not being in place, fire sprinkler coverage around fire place is adequete. Overhead fire sprinkler piping and tenting of overhead fire sprinkler piping approved for cover.
BLD16-01838 FIRE-Final Inspection9/29/20169/29/20169/29/2016 10:25:06 AMPCANC
Final life fire safety inspection cannot be completed until fire alarms and hood suppression systems have been inspected and passed. Final life safety will be scheduled for another day.
FIR16-00564 INSP-Final Inspection9/29/20169/29/20169/29/2016 10:23:52 AMPPASS
Final fire sprinkler inspection passed/complete.
FIR16-00100 INSP-Sprinkler Rough-in/Hydro9/27/20169/29/20169/29/2016 9:24:46 AMPPASS
24 hour air test for dry system complete.
BLD16-01406 FIRE-Final Inspection9/29/20169/29/20169/29/2016 9:06:42 AMAPASS
Lasr remaining item for life fire safety inspection was the racking permit, racling permit is finaled for life safety. Final life fire safety inspection passed/complete.
FIR16-00376 INSP-Final Inspection9/29/20169/29/20169/29/2016 9:02:28 AMAPASS
Final fire sprinkler inspection passed/complete.
BLD16-03245 FIRE-Final Inspection9/28/20169/29/20169/29/2016 9:01:01 AMAPASS
Final inspection for racking permit passed/complete.
BLD16-01509 FIRE-Final Inspection9/28/20169/29/20169/29/2016 8:40:41 AMAPASS
Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguishers are in common places with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00507 INSP-Final Inspection9/28/20169/29/20169/29/2016 8:39:38 AMAPASS
Final fire sprinkler inspection passed/complete
FIR16-00409 INSP-Final Inspection9/29/20169/29/20169/29/2016 8:39:09 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00360 INSP-Sprinkler Rough-in/Hydro9/28/20169/29/20169/28/2016 10:34:18 AMPCANC
Contact is Sean. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten