Inspections for the day of: Friday, September 29, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03066 Electrical Rough-In9/28/20179/29/20179/29/2017 3:10:11 PMPPASS
We are requesting a rough wall inspection for the kitchen area. Byrant, is our P.O.C. ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed new GFCI requirements. Kitchen and bar walls rough in ok cover.
ELE16-04017 Electrical Rough-In9/29/20179/29/20179/29/2017 2:37:27 PMPPASS
L4 deck pour 18 rough-in Phone #: ###-#### Inspection requested via web by Debby Pierce
Area noted rough in ok cover
ELE17-01974 Electrical Rough-In9/29/20179/29/20179/29/2017 1:45:31 PMPPASS
Contact: Ryan Mrachek - underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Underground south of building, south of curb for pole lights. Underground between bases which were not in at time of inspection. Rough in ok cover
ELE17-03251 Permanent Service9/27/20179/29/20179/29/2017 1:43:21 PMAPASS
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER
Removeable bench in front of panel.
p/s u/g rec ok
ELE17-03253 Temporary Service9/28/20179/29/20179/29/2017 11:26:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE17-03273 Electrical Rough-In9/28/20179/29/20179/29/2017 10:54:40 AMAFAIL
Phone #: ###-#### Inspection requested via web by ron spen cer
04-05-32- Code violations not to be retained. 680.21(C)- Existing pool equipment unable to locate GFCI protection.
210.52(A)(1)- Up stairs entertainment room shall have receptacle outlets located so no area is more than 6' from a receptacle outlet.
210.52(C)(1)- Main level entertainment area shall have receptacle outlets for counter top areas located so no area on counter top is more than 24" from a receptacle outlet. Counter spaces 12" or wider shall have a receptacle outlet installed.

300.5- Underground shall be 18" deep unless covered be concrete.
ELE17-02297 Final9/28/20179/29/20179/29/2017 9:22:42 AMAFAIL
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
Pool incomplete on seperate permit.
210.8- All GFCI devices shall be located in a readily accessible location. Vac over 6'7".
210.52(C)(1)- Pantry counter top shall have a receptacle outlet with in 24" of right wall.
ELE17-03269 Temporary Service9/28/20179/29/20179/29/2017 8:19:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE17-03253 Temporary Service9/28/20179/29/20179/28/2017 4:48:34 PMACANC
Phone #: ###-#### >> Inspection requested via web by Alan Lusk Inspection cancelled from web by: Alan Lusk