ELE17-03066
| Electrical Rough-In | 9/28/2017 | 9/29/2017 | 9/29/2017 3:10:11 PM | P | PASS |
|
|
We are requesting a rough wall inspection for the kitchen area. Byrant, is our P.O.C. ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate Discussed new GFCI requirements. Kitchen and bar walls rough in ok cover.
|
ELE16-04017
| Electrical Rough-In | 9/29/2017 | 9/29/2017 | 9/29/2017 2:37:27 PM | P | PASS |
|
|
L4 deck pour 18 rough-in Phone #: ###-#### Inspection requested via web by Debby Pierce Area noted rough in ok cover
|
ELE17-01974
| Electrical Rough-In | 9/29/2017 | 9/29/2017 | 9/29/2017 1:45:31 PM | P | PASS |
|
|
Contact: Ryan Mrachek - underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Underground south of building, south of curb for pole lights. Underground between bases which were not in at time of inspection. Rough in ok cover
|
ELE17-03251
| Permanent Service | 9/27/2017 | 9/29/2017 | 9/29/2017 1:43:21 PM | A | PASS |
|
|
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER Removeable bench in front of panel. p/s u/g rec ok
|
ELE17-03253
| Temporary Service | 9/28/2017 | 9/29/2017 | 9/29/2017 11:26:14 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE17-03273
| Electrical Rough-In | 9/28/2017 | 9/29/2017 | 9/29/2017 10:54:40 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer 04-05-32- Code violations not to be retained. 680.21(C)- Existing pool equipment unable to locate GFCI protection. 210.52(A)(1)- Up stairs entertainment room shall have receptacle outlets located so no area is more than 6' from a receptacle outlet. 210.52(C)(1)- Main level entertainment area shall have receptacle outlets for counter top areas located so no area on counter top is more than 24" from a receptacle outlet. Counter spaces 12" or wider shall have a receptacle outlet installed. 300.5- Underground shall be 18" deep unless covered be concrete.
|
ELE17-02297
| Final | 9/28/2017 | 9/29/2017 | 9/29/2017 9:22:42 AM | A | FAIL |
|
|
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Pool incomplete on seperate permit. 210.8- All GFCI devices shall be located in a readily accessible location. Vac over 6'7". 210.52(C)(1)- Pantry counter top shall have a receptacle outlet with in 24" of right wall.
|
ELE17-03269
| Temporary Service | 9/28/2017 | 9/29/2017 | 9/29/2017 8:19:33 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE17-03253
| Temporary Service | 9/28/2017 | 9/29/2017 | 9/28/2017 4:48:34 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk Inspection cancelled from web by: Alan Lusk
|