Inspections for the day of: Friday, September 29, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00143 Final9/29/20179/29/20179/29/2017 5:26:25 PMPPASS
J-boxes added for 4 wall sconces in master bathroom, job complete. final ok
ELE17-02659 Permanent Service9/29/20179/29/20179/29/2017 4:12:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Christy Cheney Available Fault posted and dated , P/S U/G REC OK
ELE17-01112 Final9/29/20179/29/20179/29/2017 4:12:32 PMPFAIL
Contact is James Johnston ###-#### Phone #: ###-#### Inspection requested via web by steve ragan NEC 620.23(C) At least one 125 volt 15 or 20 ampere duplex receptacle shall be provided in each machine room. Elevator car light breaker not labeled.
ELE17-01732 Rough-In Permanent Service9/28/20179/29/20179/29/2017 11:00:24 AMAPASS
Mucho Phone #: ###-#### Rough-in p/s u/g n ok
ELE17-03100 Rough-In Permanent Service9/28/20179/29/20179/29/2017 10:19:02 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough-in p/ u/g n ok
ELE17-02023 Final9/28/20179/29/20179/29/2017 9:42:45 AMAPASS
4224 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
ELE17-02659 Final9/28/20179/29/20179/29/2017 8:53:22 AMAFAIL
Phone #: ###-#### Inspection requested via web by Christy Cheney NEC 110.24 Available Fault Current shall be posted at the service.