ELE17-00143
| Final | 9/29/2017 | 9/29/2017 | 9/29/2017 5:26:25 PM | P | PASS |
|
|
J-boxes added for 4 wall sconces in master bathroom, job complete. final ok
|
ELE17-02659
| Permanent Service | 9/29/2017 | 9/29/2017 | 9/29/2017 4:12:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Christy Cheney Available Fault posted and dated , P/S U/G REC OK
|
ELE17-01112
| Final | 9/29/2017 | 9/29/2017 | 9/29/2017 4:12:32 PM | P | FAIL |
|
|
Contact is James Johnston ###-#### Phone #: ###-#### Inspection requested via web by steve ragan NEC 620.23(C) At least one 125 volt 15 or 20 ampere duplex receptacle shall be provided in each machine room. Elevator car light breaker not labeled.
|
ELE17-01732
| Rough-In Permanent Service | 9/28/2017 | 9/29/2017 | 9/29/2017 11:00:24 AM | A | PASS |
|
|
Mucho Phone #: ###-#### Rough-in p/s u/g n ok
|
ELE17-03100
| Rough-In Permanent Service | 9/28/2017 | 9/29/2017 | 9/29/2017 10:19:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough-in p/ u/g n ok
|
ELE17-02023
| Final | 9/28/2017 | 9/29/2017 | 9/29/2017 9:42:45 AM | A | PASS |
|
|
4224 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
|
ELE17-02659
| Final | 9/28/2017 | 9/29/2017 | 9/29/2017 8:53:22 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Christy Cheney NEC 110.24 Available Fault Current shall be posted at the service.
|