Inspections for the day of: Wednesday, September 3, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00137 FIRE-Final Inspection8/28/20039/3/20039/3/2003 12:00:00 AMAPASS
Fire life safety is ok. Owner to hang the two existing fire extinguishers this morning. One wall that was to be demo'd is to remain 9/3/2003 10:28:47 AM
BLD03-00475 FIRE-Final Inspection9/2/20039/3/20039/3/2003 12:00:00 AMAFAIL
The remote alarm/trouble leds that were to be provided do not annunciate a trouble condition. I spoke with the electrical contractor about the correct model to use. 9/3/2003 1:12:07 PM
FIR03-00062 INSP-Final Inspection9/2/20039/3/20039/3/2003 12:00:00 AMAPASS
ralp; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00062 INSP-Final Inspection9/2/20039/3/20039/3/2003 12:00:00 AMAPASS
ralp; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00090 INSP-Sprinkler Rough-in9/2/20039/3/20039/3/2003 12:00:00 AMAPART
The iniatial long section of 3" main need EQ bracing. Electrical and communications contractors to remove wiring from sprinkler pipe hangers. Sprinkler rough-in is OK
9/3/2003 12:13:24 PM 9/3/2003 12:13:53 PM
FIR03-00374 INSP-Sprinkler Rough-in9/3/20039/3/20039/3/2003 12:00:00 AMPPART
The rest of the underground supply piping is ok to cover 9/3/2003 4:31:48 PM