BLD02-00137
| FIRE-Final Inspection | 8/28/2003 | 9/3/2003 | 9/3/2003 12:00:00 AM | A | PASS |
|
|
Fire life safety is ok. Owner to hang the two existing fire extinguishers this morning. One wall that was to be demo'd is to remain 9/3/2003 10:28:47 AM
|
BLD03-00475
| FIRE-Final Inspection | 9/2/2003 | 9/3/2003 | 9/3/2003 12:00:00 AM | A | FAIL |
|
|
The remote alarm/trouble leds that were to be provided do not annunciate a trouble condition. I spoke with the electrical contractor about the correct model to use. 9/3/2003 1:12:07 PM
|
FIR03-00062
| INSP-Final Inspection | 9/2/2003 | 9/3/2003 | 9/3/2003 12:00:00 AM | A | PASS |
|
|
ralp; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR03-00062
| INSP-Final Inspection | 9/2/2003 | 9/3/2003 | 9/3/2003 12:00:00 AM | A | PASS |
|
|
ralp; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR03-00090
| INSP-Sprinkler Rough-in | 9/2/2003 | 9/3/2003 | 9/3/2003 12:00:00 AM | A | PART |
|
|
The iniatial long section of 3" main need EQ bracing. Electrical and communications contractors to remove wiring from sprinkler pipe hangers. Sprinkler rough-in is OK
9/3/2003 12:13:24 PM 9/3/2003 12:13:53 PM
|
FIR03-00374
| INSP-Sprinkler Rough-in | 9/3/2003 | 9/3/2003 | 9/3/2003 12:00:00 AM | P | PART |
|
|
The rest of the underground supply piping is ok to cover 9/3/2003 4:31:48 PM
|