Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00946 ELE-Aging Inspection9/3/20089/3/20089/4/2008 4:17:42 PM PART
wsuc
ESC08-00259 General Inspection9/3/20089/3/20089/3/2008 3:38:35 PMPPART
ok
ELE08-02415 Rough-In Permanent Service9/2/20089/3/20089/3/2008 3:37:55 PMPPART
Home is off Broadway @ richmond Phone #: ###-#### Internet Inspection Request from: Joe Thomascalled r/i ok only, p/s pending , it was inspected but needs u/g uncovered for inspection before p/s can be tagged
ELE08-01787 Electrical Rough-In9/3/20089/3/20089/3/2008 2:53:41 PMPFAIL
Shane- cabinet rough-in pharmacy Phone #: ###-#### corr talked with contr. pharmacy, box fill, starbucks box fill secure all cables and flex, grd all boxes, over 360 degrees of bends in flex
ESC08-00039 General Inspection9/3/20089/3/20089/3/2008 2:10:48 PMPPART
ok
ELE08-01135 Final9/3/20089/3/20089/3/2008 2:10:12 PMPPASS
tom Phone #: ###-#### ok
ELE08-01449 Electrical Rough-In9/2/20089/3/20089/3/2008 1:34:31 PMPPART
Electrical Roughin ( Walls Only ) Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe living unit only walls and ceilings, no common area anop
ELE08-02120 Electrical Rough-In9/2/20089/3/20089/3/2008 10:23:51 AMAPART
Wall and underground inspection. Chris is the contact electrician, his # is ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Shawna Gates
ok anop
ELE08-01389 Final9/3/20089/3/20089/3/2008 9:49:52 AMAPASS
ELE08-01259 Final9/2/20089/3/20089/3/2008 9:21:53 AMAFAIL
Thomas ###-#### job not ready, needs main breaker for p/s, all boxes shall be flush with wood finish, needs gfci for recepts, isolate grds and neutrals at p/s
ELE08-02427 Permanent Service9/2/20089/3/20089/3/2008 8:30:17 AMAPASS
#90733,Q#8231AzN. Wired a new power pedestal & phone cabinet for QWEST.
This is in the alley, north of Haines.
James ###-####. Phone #: ###-####
Internet Inspection Request from: Dan Mitchell p/s u/g new ok
ELE08-02427 Final9/3/20089/3/20089/3/2008 8:29:18 AMAPASS
#90733,Q#8231AzN. Wired a new power pedestal & phone cabinet for QWEST.
This is in the alley, north of Haines.
James ###-####. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell