Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00386 INSP-Final Inspection9/3/20099/3/20099/8/2009 3:19:18 PMPNR
Incompleted work on 9/3.
FIR09-00261 INSP-Sprinkler Rough-in/Hydro9/3/20099/3/20099/4/2009 7:08:55 AMPPART
Overhead hydrostatic testing passed. Overhead rough-in inspection completed satisfactory, items incomplete include sprinklers under overhead doors at the wash bay and pressure relief valve at the riser.
FIR08-00815 INSP-Final Inspection9/3/20099/3/20099/3/2009 11:46:39 AMAFAIL
Need to remove travel cap and install escutcheon at one pendent head at a first floor bedroom, replace one exposed recessed head with the correct type for the application, repair non-functional outside bell, provide missing sprinklers at the head box, lock or seal control valves in the open position at the backflow preventer.
FIR09-00306 FIR-Aging Inspection9/3/20099/3/20099/3/2009 11:40:17 AM DONE
Work in progress, construction underway.
BLD09-01429 FIRE-Final Inspection9/2/20099/3/20099/3/2009 11:39:44 AMAPASS
Vanilla permit work passed fire life safety inspection.
BLD06-01199 FIRE-Final Inspection9/2/20099/3/20099/3/2009 11:38:53 AMAFAIL
All items on the previously issued correction notice remain undone including door hardware at four locations, building address and missing plans with the exception of fire extinguishers which have been tagged, however are due re-certification this month.
BLD09-00012 FIRE-Final Inspection9/2/20099/3/20099/3/2009 11:35:38 AMAPASS
Life safety inspection passed.
BLD09-01301 FIRE-Final Inspection9/2/20099/3/20099/3/2009 11:34:55 AMACANC
Overbooked
FIR09-00505 INSP-Final Inspection9/2/20099/3/20099/3/2009 11:32:26 AMACANC
Overbooked
FIR09-00463 INSP-Final Inspection9/1/20099/3/20099/3/2009 11:32:02 AMACANC
Overbooked
BLD09-01156 FIRE-Final Inspection9/2/20099/3/20099/3/2009 11:31:40 AMACANC
Overbooked
FIR08-00815 INSP-Final Inspection9/2/20099/3/20099/3/2009 10:15:45 AMACANC
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick