FIR13-00313
| INSP-Final Inspection | 8/30/2013 | 9/3/2013 | 9/3/2013 3:27:20 PM | P | FAIL |
|
|
Instead of two uprights in the canopy, side walls have been installed which is ok. Issues are a small room has been built and has no sprinkler protection. Also several pendants have been painted and need to be replaced. Annual inspections have expired for both the wet and anti-freeze sprinkler systems. I told scott I would be ok with as-builts showing the changes/addition.
|
BLD13-02341
| FIRE-Final Inspection | 9/3/2013 | 9/3/2013 | 9/3/2013 3:20:13 PM | P | CANC |
|
|
The corrections have not been addressed through a fire alarm permit. To be rescheduled
|
BLD13-01745
| FIRE-Final Inspection | 8/30/2013 | 9/3/2013 | 9/3/2013 9:44:37 AM | A | PART |
|
|
A temp occ for north side of building first floor is approved with scotts permission. See tide mark entry for conditions/exiting. Emergency lighting on the second and third floors was verified.
|
BLD13-01619
| FIRE-Final Inspection | 8/30/2013 | 9/3/2013 | 9/3/2013 9:32:38 AM | A | PART |
|
|
Life safety complete in Building #2, 2104 Front. Exit signs have been installed and hardware removed from the in-active leaf.
|