ELE12-01275
| ELE-Aging Inspection | 9/3/2014 | 9/3/2014 | 9/3/2014 2:12:34 PM | | DONE |
|
|
still under construction
|
ELE14-02362
| Electrical Rough-In | 9/3/2014 | 9/3/2014 | 9/3/2014 2:08:29 PM | P | PASS |
|
|
We are requesting an underground inspection for this afternoon. Our onsite contact is Luke Hardy @ ###-####. Thank you! Phone #: ###-#### >> Inspection requested via web by Clint Tate ok pour concrete encased electrode
|
ELE13-02953
| Final | 9/2/2014 | 9/3/2014 | 9/3/2014 1:34:27 PM | P | PASS |
|
|
Clyde Phone #: ###-#### ok final
|
ELE14-02324
| Final | 9/3/2014 | 9/3/2014 | 9/3/2014 12:07:15 PM | P | PASS |
|
|
call ###-#### for access code Phone #: ###-#### >> Inspection requested via web by David Nelson ok final
|
ELE14-01823
| Final | 9/2/2014 | 9/3/2014 | 9/3/2014 10:50:02 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Celinda Winters ok final
|
ELE14-02347
| Final | 9/2/2014 | 9/3/2014 | 9/3/2014 10:31:30 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Celinda Winters ok final
|
ELE14-02406
| Electrical Rough-In | 9/1/2014 | 9/3/2014 | 9/3/2014 9:57:02 AM | A | FAIL |
|
|
if you have questions please call eric at ###-#### We have not done the service yet waiting for some material Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 334.23 shall protect nm cable within 6' of attic access, 334.30 shall secure nm cable every 4 1/2' and within 12" of box, 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member or use steel plate, 210.52(A)(1) receptacles shall be installed such that no point along floor line is more than 6' from outlet, BCC shall provide boxes for free conductors #12 and #14l
|
ELE14-02418
| Rough-In Permanent Service | 9/2/2014 | 9/3/2014 | 9/3/2014 9:06:22 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|
ELE14-01572
| Final | 9/2/2014 | 9/3/2014 | 9/3/2014 8:23:47 AM | A | PASS |
|
|
GARAGE CODE 4224 Phone #: ###-#### >> Inspection requested via web by Bob Glenn ok final
|