Inspections for the day of: Wednesday, September 3, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02100 Final9/2/20149/3/20149/3/2014 1:09:09 PMPPASS
###-#### / Final inspection requested Phone #: ###-#### Inspection requested via web by jamie berg final ok
ELE12-03018 Final9/3/20149/3/20149/3/2014 12:40:54 PMPPASS
Sign no longer exsist, changed business. final ok
ELE12-03074 ELE-Aging Inspection9/3/20149/3/20149/3/2014 12:26:34 PM DONE
see final
ELE12-03074 Final9/3/20149/3/20149/3/2014 12:25:59 PMPPASS
UL listed sign, final ok
ELE14-02422 Permanent Service9/3/20149/3/20149/3/2014 12:19:22 PMPPASS
Larry Phone #: ###-#### p/s u/g rec ok
ELE14-01986 Permanent Service9/3/20149/3/20149/3/2014 11:54:04 AMPPASS
Rick Phone #: ###-#### p/s u/g rec ok
ELE14-01284 Final9/2/20149/3/20149/3/2014 11:13:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by Steve Craig A/C unit requires wiring rated for wet locations, Furnace requires labeled disconnect or breaker lockout, Receptacle in wine cellar requires equipment grounding connection, Panel directory too brief.
ELE14-02427 Final9/2/20149/3/20149/3/2014 10:05:28 AMAPASS
Contact is Justin Metcalf ###-####. Thank you and have a great day! Phone #: ###-#### Inspection requested via web by Laura Longshaw final ok
GCE14-00134 GCE-Temporary Service9/2/20149/3/20149/3/2014 9:29:45 AMAPASS
Brandon ###-#### t/s u/g n ok
GCE14-00132 GCE-Temporary Service9/2/20149/3/20149/3/2014 9:28:53 AMAPASS
Brandon ###-#### t/s u/g n ok
GCE14-00103 GCE-Final9/2/20149/3/20149/3/2014 8:54:35 AMAFAIL
Daniel ###-#### NEC 210.8 (A)(2) and (7) All 15 and 20 ampere 120 volt receptacles located in garages and receptacles located within 6ft. of an sink (laundry room) require GFCI protection.