Inspections for the day of: Thursday, September 3, 2015.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00751 INSP-Sprinkler Rough-in/Hydro9/2/20159/3/20159/3/2015 11:31:45 AMAPASS
Hydrostatic test (200 psi @ 2hours) for the wet pipe system for Bldg. L. Some hard-lid areas of the wet system have already been covered, although contractor has stated that these areas were inspected prior to this inspection. No inspection of these areas were recorded on the plans, which is the typical process.
Hydrotest PASSED
FIR14-00751 INSP-Sprinkler Rough-in9/2/20159/3/20159/3/2015 11:31:26 AMAPART
Rough to cover inspection for wet pipe hard lids - some CPVC pipe already covered - contractor stated that was inspected at an earlier inspection, although this was not indicated on the plans. Wet system under hydrotest also during this inspection.
FIR14-00477 INSP-Final Inspection9/2/20159/3/20159/3/2015 10:14:19 AMAPASS
Final inspection of the fire service U/G supply to the building - PASSED. Contractor cert. of completion signed off and will be emailed to the PDS office.
FIR14-00603 INSP-Final Inspection9/2/20159/3/20159/3/2015 10:13:07 AMAPASS
Final inspection of fire sprinklers for the parking garage area of the building - PASSED. Contractor cert. of completion signed off and will be emailed to the PDS office.
FIR14-00815 INSP-Final Inspection9/2/20159/3/20159/3/2015 10:11:48 AMAPASS
Final inspection of fire sprinklers for the above parking lot areas of the building - PASSED. Contractor cert. of completion signed off and will be emailed to the PDS office.
FIR14-00478 INSP-Final Inspection9/2/20159/3/20159/3/2015 10:07:06 AMAPASS
Final inspection of fire service U/G supply.
PASSED
NOTE: Heat tracing of wet pipe bulk mains running through parking garage has been determined not to be required.