FIR15-00143
| INSP-Final Inspection | 9/3/2015 | 9/3/2015 | 9/3/2015 3:59:22 PM | P | FAIL |
|
|
No sprinklers covering under the two overhead doors located inside of the cooler section, needs sprinkler coverage. No ball drip on FDC. Need specifications on air compressor installed on dry system to see if it meets the requirements of 7.2.6.6.2-air compressor supplying dry pipe system has a capacity of less the 5.5 cubic feet at 10 psi, currently no air maintenance on dry system and contractor is referencing mentioned code from NFPA13.
|
FIR15-00354
| INSP-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 3:11:42 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR15-00530
| INSP-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 2:00:10 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD15-00982
| FIRE-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 1:25:03 PM | A | FAIL |
|
|
Called phone number provided, ###-####, at 9:54am, no one answered, left message with contact information, no return call, inspection failed.
|
FIR15-00153
| INSP-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 12:24:50 PM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD15-02703
| FIRE-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 10:59:40 AM | A | PASS |
|
|
Life fire safety passed/complete for racking permit
|
BLD15-00319
| FIRE-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 10:28:09 AM | A | PASS |
|
|
Life fire safety passed/complete
|
BLD14-02890
| FIRE-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 9:50:49 AM | A | PASS |
|
|
Fire sprinkler located in walk in cooler, life fire safety passed/complete
|
FIR15-00472
| INSP-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 9:47:16 AM | A | CANC |
|
|
Called Sam, at phone # ###-####, inspection will be rescheduled to coincide with alarm inspection and life fire safety inspection.
|
BLD15-00999
| FIRE-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 9:41:31 AM | P | CANC |
|
|
Alarm permit not called in for inspection, need to final alarm inspection before life fire safety can be completed.
|
FIR15-00489
| INSP-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 9:21:31 AM | A | CANC |
|
|
Duplicate inspection, final inspection completed
|
BLD15-01685
| FIRE-Final Inspection | 9/3/2015 | 9/3/2015 | 9/3/2015 9:19:51 AM | P | PASS |
|
|
Life fire safety passed/complete
|
FIR15-00505
| INSP-Final Inspection | 9/3/2015 | 9/3/2015 | 9/3/2015 9:15:47 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00489
| INSP-Final Inspection | 9/1/2015 | 9/3/2015 | 9/3/2015 9:13:46 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD15-03014
| FIRE-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 8:39:39 AM | A | PASS |
|
|
Life fire safety passed/complete
|