Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00143 INSP-Final Inspection9/3/20159/3/20159/3/2015 3:59:22 PMPFAIL
No sprinklers covering under the two overhead doors located inside of the cooler section, needs sprinkler coverage. No ball drip on FDC. Need specifications on air compressor installed on dry system to see if it meets the requirements of 7.2.6.6.2-air compressor supplying dry pipe system has a capacity of less the 5.5 cubic feet at 10 psi, currently no air maintenance on dry system and contractor is referencing mentioned code from NFPA13.
FIR15-00354 INSP-Final Inspection9/2/20159/3/20159/3/2015 3:11:42 PMPPASS
Final fire alarm inspection passed/complete
FIR15-00530 INSP-Final Inspection9/2/20159/3/20159/3/2015 2:00:10 PMPPASS
Final fire alarm inspection passed/complete
BLD15-00982 FIRE-Final Inspection9/2/20159/3/20159/3/2015 1:25:03 PMAFAIL
Called phone number provided, ###-####, at 9:54am, no one answered, left message with contact information, no return call, inspection failed.
FIR15-00153 INSP-Final Inspection9/2/20159/3/20159/3/2015 12:24:50 PMAPASS
Final fire alarm inspection passed/complete
BLD15-02703 FIRE-Final Inspection9/2/20159/3/20159/3/2015 10:59:40 AMAPASS
Life fire safety passed/complete for racking permit
BLD15-00319 FIRE-Final Inspection9/2/20159/3/20159/3/2015 10:28:09 AMAPASS
Life fire safety passed/complete
BLD14-02890 FIRE-Final Inspection9/2/20159/3/20159/3/2015 9:50:49 AMAPASS
Fire sprinkler located in walk in cooler, life fire safety passed/complete
FIR15-00472 INSP-Final Inspection9/2/20159/3/20159/3/2015 9:47:16 AMACANC
Called Sam, at phone # ###-####, inspection will be rescheduled to coincide with alarm inspection and life fire safety inspection.
BLD15-00999 FIRE-Final Inspection9/2/20159/3/20159/3/2015 9:41:31 AMPCANC
Alarm permit not called in for inspection, need to final alarm inspection before life fire safety can be completed.
FIR15-00489 INSP-Final Inspection9/2/20159/3/20159/3/2015 9:21:31 AMACANC
Duplicate inspection, final inspection completed
BLD15-01685 FIRE-Final Inspection9/3/20159/3/20159/3/2015 9:19:51 AMPPASS
Life fire safety passed/complete
FIR15-00505 INSP-Final Inspection9/3/20159/3/20159/3/2015 9:15:47 AMPPASS
Final fire sprinkler inspection passed/complete
FIR15-00489 INSP-Final Inspection9/1/20159/3/20159/3/2015 9:13:46 AMAPASS
Final fire alarm inspection passed/complete
BLD15-03014 FIRE-Final Inspection9/2/20159/3/20159/3/2015 8:39:39 AMAPASS
Life fire safety passed/complete