Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01947 ELE-Aging Inspection9/30/20039/30/20039/30/2003 12:00:00 AM FAIL
no access to equip rm 9/30/2003 12:34:13 PM
ELE03-00057 Final9/29/20039/30/20039/30/2003 12:00:00 AMANR
Scheduled by a contractor via Hello! on 9/29/2003 at 8:01:13 AM. Contact: ###-####. no SMS roof top disconnects 250.8,
open grds and neutrals recepts through out called 9/30/2003 12:33:15 PM
ELE03-03035 Electrical Rough-In9/29/20039/30/20039/30/2003 12:00:00 AMAFAIL
dan; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted called 300.4 (A)(1)&(D), 210.52(A), 334.24, 110.12(A) replace 2&3 gang boxes with broken clamps, 314.16 cutin switch box for fan 9/30/2003 9:35:11 AM
ELE03-02824 Electrical Rough-In9/29/20039/30/20039/30/2003 12:00:00 AMAPART
ron-801- ###-#### grd ring ok 9/30/2003 8:05:45 AM
ELE03-02906 Electrical Rough-In9/29/20039/30/20039/30/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/29/2003 at 12:32:41 PM. Contact: ###-####. walls ok 9/30/2003 9:59:26 AM
ELE03-03041 Final9/29/20039/30/20039/30/2003 12:00:00 AMANR
###-#### ryan needs p/s shall provide light for service, needs to wire shop called 9/30/2003 10:48:28 AM
ELE03-02755 Final9/29/20039/30/20039/30/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/29/2003 at 3:00:51 PM. Contact: ###-####. ok 9/30/2003 7:36:08 AM
ELE03-03020 Electrical Rough-In9/29/20039/30/20039/30/2003 12:00:00 AMAPASS
Access through the back of the house. No dogs in backyard.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok 9/30/2003 8:37:07 AM
ELE03-02708 Electrical Rough-In9/29/20039/30/20039/30/2003 12:00:00 AMAFAIL
ron; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called left message needs concrete encased electrode installed, 334.15 protect romex , 250.32(B)(1) remove bond screw 9/30/2003 10:20:00 AM
ELE03-03038 Rough-In Permanent Service9/29/20039/30/20039/30/2003 12:00:00 AMPPASS
kevin; Phone #: ###-#### Internet Inspection Request from: Darla Downs
p/s o/h rec. ok 9/30/2003 3:33:58 PM
ELE03-03004 Permanent Service9/29/20039/30/20039/30/2003 12:00:00 AMPPASS
mitch; Phone #: ###-#### Internet Inspection Request from: Annette Moore
p/s o/h rec. ok 9/30/2003 2:52:36 PM