FIR03-00369
| INSP-Final Inspection | 9/29/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/29/2003 at 12:16:46 PM. Contact: ###-####.
|
BLD03-00482
| FIRE-Final Inspection | 9/29/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | A | FAIL |
|
|
need fire alarm finaled, lower and tag fire extinguishers, provide building address and suite numbers, install fire hydrant (I'm expecting a call from united water) 9/30/2003 12:05:17 PM
|
FIR03-00357
| INSP-Alarm Testing | 9/29/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | A | FAIL |
|
|
Provide NFPA forms, provide signage on door, 5amp battery needs supervised, verify current draw, mount map at facp 9/30/2003 12:04:04 PM
|
BLD03-01334
| FIRE-Final Inspection | 9/29/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | A | CANC |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD03-01805
| FIRE-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 9/30/2003 2:46:08 PM
|
BLD03-01324
| FIRE-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | CANC |
|
|
duplicate inspection 9/30/2003 2:22:26 PM
|
FIR03-00216
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | FAIL |
|
|
fire alarm signals are still not being reported correctly or the monitoring company does not know what they are doing. 9/30/2003 3:52:04 PM
|
FIR03-00276
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | FAIL |
|
|
inspection not done since the main fire alarm system is not reporting correctly. I stopped the inspection 9/30/2003 3:50:56 PM
|
FIR03-00267
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | FAIL |
|
|
inspection not done since the main fire alarm system is not reporting correctly. I stopped the inspection 9/30/2003 3:51:17 PM
|
FIR03-00277
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | CANC |
|
|
wrong inspection called in 9/30/2003 3:49:44 PM
|
FIR03-00268
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | CANC |
|
|
wrong inspection called in 9/30/2003 3:49:55 PM
|
FIR03-00499
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | FAIL |
|
|
pendants are overspace and do not match plans in the cafe area, provide pendant by managers office, install tile in stockroom 9/30/2003 2:21:26 PM
|
BLD03-01334
| FIRE-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | PART |
|
|
dennis; Phone #: ###-#### A temporary occupancy is being given with dave millers permission until the fire alarm plans have been approved and the installation has been inspected. All other life safety items are ok 9/30/2003 3:48:39 PM
|
FIR03-00289
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | PASS |
|
|
|
BLD03-01324
| FIRE-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | FAIL |
|
|
Correct exit sign near rear stock room(it should point to the east exit), Post occupancy load signs, verify annual sprinkler inspection, final sprinklers
|
FIR03-00588
| INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | PART |
|
|
A temporary occupancy is being given with dave millers permission until the fire alarm plans have been approved and the installation has been inspected
|
FIR03-00418
| INSP-Sprinkler Rough-in/Hydro | 9/30/2003 | 9/30/2003 | 9/30/2003 12:00:00 AM | P | PASS |
|
|
|