Inspections for the day of: Thursday, September 30, 2004.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01905 FIRE-Final Inspection9/29/20049/30/20049/30/2004 12:00:00 AMAPART
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Temp occupancy for fire pending upgrade of fire sprinkler monitoring and HVAC detector system 9/30/2004 8:28:29 AM
FIR04-00580 INSP-Sprinkler Rough-in9/29/20049/30/20049/30/2004 12:00:00 AMAFAIL
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Okay to cover - per plans; need Reliable QR heads in spare head box 9/30/2004 10:12:49 AM
FIR04-00208 INSP-Conference9/30/20049/30/20049/30/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 9/30/2004 at 8:39:22 AM. Contact: ###-####. Met with Doug about hose outlet placement - install as shown on plans - except on first tier the outlet shall be turned to 45 degrees to allow access 9/30/2004 2:12:37 PM
BLD03-01219 FIRE-Final Inspection9/30/20049/30/20049/30/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/30/2004 at 10:09:14 AM. Contact: ###-####.
FIR04-00167 INSP-Sprinkler Rough-in/Hydro9/30/20049/30/20049/30/2004 12:00:00 AMPFAIL
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Sub-basment failed hydro; ground hydro okay 9/30/2004 3:42:27 PM
MIS04-00262 FIR-Final9/30/20049/30/20049/30/2004 12:00:00 AMPFAIL
reham--pending fire fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie fire extinguishers at each level; one exit required as tenant is to maintain 50 occupants; basement not to be used; architect to draw up plans by 12/04 per permit application requirements; post address 9/30/2004 3:05:12 PM