Inspections for the day of: Friday, September 30, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-03049 FIRE-Final Inspection9/29/20059/30/20059/30/2005 4:58:37 PMPCANC
Cancel inspection per Russ the general contractor.
FIR05-00273 INSP-Final Inspection9/30/20059/30/20059/30/2005 2:43:38 PMPFAIL
The resubmitted plans for field changes still do not match the installation as required, the first floor main and riser room locations are not accurate showing on opposite sides of the building from the actual install.
FIR05-00633 INSP-Final Inspection9/30/20059/30/20059/30/2005 1:24:55 PMPPASS
Fire sprinkler passed final inspection, permit finaled.
FIR05-00428 INSP-Sprinkler Rough-in9/29/20059/30/20059/30/2005 12:55:08 PMAPART
Relocated heads in storage room 132, EQ bracing in corridor, and head at north entry vestibule are acceptable.
BLD05-01033 FIRE-Final Inspection9/29/20059/30/20059/30/2005 12:52:22 PMAFAIL
Provide signage above main entry/exit doors stating " this door to remain unlocked while building is occupied", repair non functioning emergency light, install and tag fire extinguisher as discussed.
FIR05-00520 INSP-Sprinkler Rough-in/Hydro9/29/20059/30/20059/30/2005 11:11:54 AMAPART
Branch line directly above electrical panel needs to be relocated, the remainder of overhead rough-in is good for cover.
BLD05-02312 FIRE-Final Inspection9/29/20059/30/20059/30/2005 9:48:31 AMAPASS
Fire life safety passed inspection.
MIS05-00158 FIR-Final9/29/20059/30/20059/30/2005 9:47:18 AMAPASS
Issues on correction notice have been addressed, fire life safety acceptable.
BLD05-01033 FIRE-Final Inspection9/30/20059/30/20059/30/2005 12:00:00 AMPPASS
Fire life safety finaled.