Inspections for the day of: Wednesday, September 30, 2009.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01858 Electrical Rough-In9/30/20099/30/20099/30/2009 4:04:22 PMPPASS
Please provide electrical underground inspection. Contact person is Craig at ###-####. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok to cover u/g from torch to light pole west only, no esc this project
ESC09-00235 General Inspection9/30/20099/30/20099/30/2009 4:02:31 PMPPASS
looked ok
ESC08-00457 General Inspection9/30/20099/30/20099/30/2009 3:39:58 PMPPASS
looked ok for front of building only
ESC07-00469 General Inspection9/30/20099/30/20099/30/2009 3:14:42 PMPPASS
looked ok, still planted to weeds in back 1/2 yard
ESC09-00591 General Inspection9/30/20099/30/20099/30/2009 2:48:05 PMPPASS
looked ok
ESC09-00181 General Inspection9/30/20099/30/20099/30/2009 2:12:30 PMPPASS
looked ok
ELE08-02536 Electrical Rough-In9/30/20099/30/20099/30/2009 1:49:24 PMPPASS
Requesting a re inspection of the dental office. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty walls only ok to cover
ELE09-01855 Final9/29/20099/30/20099/30/2009 12:42:28 PMPPASS
Tom ( ref ELE07-03349 ) Phone #: ###-#### ok to final, talked to contractor
ELE09-01856 Electrical Rough-In9/30/20099/30/20099/30/2009 12:38:56 PMPCANC
Re Inspect Phone #: ###-#### Internet Inspection Request from: Jenni Keller Inspection cancelled from web by: Jenni Keller Inspection cancelled from web by: Jenni Keller
ELE09-01856 Electrical Rough-In9/29/20099/30/20099/30/2009 10:42:18 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jenni Keller called, lef tcorrection notice, NEC 110.12(B) box shall not be damaged or broken, 250.86 metal enclosure shall be connected to the equipment grounding conductor, no esc this project
ELE09-01828 Electrical Rough-In9/28/20099/30/20099/30/2009 10:00:36 AMAPASS
Bonding inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers pool bonding only ok, no u/g seen
ELE09-01541 Permanent Service9/29/20099/30/20099/30/2009 9:15:48 AMAPASS
late morning, call first Phone #: ###-#### Internet Inspection Request from: PAT MILLER p/s u/g rec ok, no esc this project
ELE09-01826 Permanent Service9/29/20099/30/20099/30/2009 9:03:50 AMAPASS
Scheduled by a contractor via Hello! on 9/29/2009 at 12:34:34 PM. Contact: ###-####. p/s u/g n ok
ELE09-01251 Final9/29/20099/30/20099/30/2009 8:33:05 AMAPASS
Jim is the contact his no. is ###-####. Phone #: ###-#### Internet Inspection Request from: Shawna Gates ok to final