Inspections for the day of: Friday, September 30, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00483 INSP-Sprinkler Rough-in/Hydro9/30/20119/30/20119/30/2011 4:45:09 PMPPASS
UG fire supply line hydrostatic testing passed.
FIR11-00186 INSP-Alarm Testing9/29/20119/30/20119/30/2011 4:07:01 PMAPART
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson
FIR11-00414 INSP-Sprinkler Rough-in/Hydro9/29/20119/30/20119/30/2011 3:07:01 PMPPASS
UG fire supply line hydrostatic test passed.
FIR11-00026 INSP-Final Inspection9/29/20119/30/20119/30/2011 2:42:50 PMAFAIL
The auxiliary power supply arrangement for the IPDACT does not meet product installation guidelines. Wiring must be in accordance with NFPA 70 and 72. Address correction for account monitoring completed while on site.
BLD11-01345 FIRE-Final Inspection9/30/20119/30/20119/30/2011 12:31:04 PMPPASS
Fire life safety finaled.
BLD11-01627 FIRE-Final Inspection9/28/20119/30/20119/30/2011 12:29:45 PMAPASS
C/N items finished. Fire life safety inspection passed.
FIR11-00447 INSP-Final Inspection9/29/20119/30/20119/30/2011 12:28:38 PMAPASS
Correction items verified for completion. Fire alarm permit finaled.
BLD10-02862 FIRE-Final Inspection9/29/20119/30/20119/30/2011 10:42:32 AMAPASS
Fire life safety inspection passed.
FIR11-00355 INSP-Sprinkler Rough-in9/28/20119/30/20119/30/2011 10:17:50 AMAFAIL
Upright heads at the first floor corridor are blocked by adjacent truss webs due to distance of the deflector from the deck, two pendent heads at classroom 201 need to meet fig. 8.6.5.1.2(b) NFPA 13, storage room 204 uprights are obstructed by ductwork. Remainder of drop ceiling areas are okay for cover.