Inspections for the day of: Friday, September 30, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00015 FIR-Aging Inspection9/30/20119/30/201110/6/2011 8:40:23 AM NR
I forwarded this permit number and status to scott for further action.
BLD10-02870 FIRE-Final Inspection9/28/20119/30/20119/30/2011 3:37:12 PMAFAIL
This project was not ready for life safety inspection but mike and I went over life safety items that will need addressed such as an "opticon" for the electric gate.
BLD11-02132 FIRE-Final Inspection9/30/20119/30/20119/30/2011 3:33:49 PMPFAIL
See the red line comments on the city approved plans for correction items. They include painting the address, repairing the exit signs, providing exit discharge lighting and providing single action hardware.
FIR11-00399 INSP-Final Inspection9/30/20119/30/20119/30/2011 2:48:37 PMPFAIL
Tested the flow switch, tamper #1 and main lobby pull station. Paul received the signals from the relays but no informaton from the intela tap came in.
BLD11-01879 FIRE-Final Inspection9/30/20119/30/20119/30/2011 2:09:40 PMPPASS
Life safety passed.
BLD10-02666 FIRE-Conference9/30/20119/30/20119/30/2011 2:09:03 PMPDONE
Spoke to the insulation contractor about providing the necessary access points to verify that the combustible concealed spaced are completely filled with noncombustible insulation.
FIR11-00508 INSP-Sprinkler Rough-in9/29/20119/30/20119/30/2011 12:42:15 PMAFAIL
No inspection was performed due to the ceiling tile being installed.
FIR11-00464 INSP-Supply line flush9/29/20119/30/20119/30/2011 11:29:44 AMAPASS
The supply line flush passed.
FIR11-00529 INSP-Final Inspection9/29/20119/30/20119/30/2011 11:26:43 AMAFAIL
One of the new pendants installed in the corridor has been placed less than 6' from an existing pendant. Other heads are ok.
BLD09-00832 FIRE-Final Inspection9/29/20119/30/20119/30/2011 11:16:14 AMAFAIL
Provide fire dept access curb painting as discussed.
BLD11-01879 FIRE-Final Inspection9/29/20119/30/20119/30/2011 10:09:59 AMAFAIL
Provide smoke detector at the north exit as per plans and provide the required exit sign/emergency lighting and exit discharge lighting per plans. Per Sam the exit signs in the classrooms can be deleted since the occupant load does not exceed 10.