Inspections for the day of: Tuesday, September 30, 2014.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01656 ELE-Aging Inspection9/30/20149/30/201410/2/2014 2:31:30 PM DONE
Still under construction
ELE14-01539 Electrical Rough-In9/30/20149/30/20149/30/2014 3:10:19 PMPFAIL
Jalal// please call before Phone #: ###-#### 250.96 Bonding Other Enclosures.
(A) General. Metal raceways, cable trays, cable armor,
cable sheath, enclosures, frames, fittings, and other metal
non–current-carrying parts that are to serve as equipment
grounding conductors, with or without the use of supplementary
equipment grounding conductors, shall be bonded
where necessary to ensure electrical continuity and the capacity
to conduct safely any fault current likely to be imposed on them.
210.11(C)(3) Bathroom Branch Circuits. In addition to the number
of branch circuits required by other parts of this section, at
least one 120-volt, 20-ampere branch circuit shall be provided
to supply a bathroom receptacle outlet(s). Such circuits
shall have no other outlets.
210.52(A)(2) Wall Space. As used in this section, a wall space shall
include the following:
(1) Any space 600 mm (2 ft) or more in width (including
space measured around corners) and unbroken along
the floor line by doorways and similar openings, fireplaces,
and fixed cabinets.
300.4 Protection Against Physical Damage. Where subject
to physical damage, conductors, raceways, and cables
shall be protected.
334.30-Flat cables shall not be
stapled on edge.
110.3- Smoke detector wiring shall be complete.
ELE14-01539 Permanent Service9/30/20149/30/20149/30/2014 2:52:21 PMPPASS
Jalal// please call before Phone #: ###-#### p/s o/h n ok
ELE14-02700 Electrical Rough-In9/29/20149/30/20149/30/2014 2:34:25 PMPPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton East office walls only rough in ok cover
ELE14-02682 Rough-In Permanent Service9/29/20149/30/20149/30/2014 1:46:23 PMPPASS
If you have any questions, please call the office. Thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Rough in ok cover p/s u/g n ok
ELE14-02686 Electrical Rough-In9/26/20149/30/20149/30/2014 1:14:11 PMPPASS
Converted electric furnace to gas-job complete need final Inspection requested via web by Stuart Welton Rough in ok
ELE14-02686 Final9/30/20149/30/20149/30/2014 1:13:25 PMPPASS
Converted electric furnace to gas-job complete need final Inspection requested via web by Stuart Welton Final ok
ELE14-02207 Final9/30/20149/30/20149/30/2014 12:53:48 PMPNR
Phone #: ###-#### Inspection requested via web by daniel bibikov Requested wrong address. this unit not ready
GCE14-00127 GCE-Rough-In9/30/20149/30/20149/30/2014 12:08:26 PMPPASS
Art ###-#### trench inspection requested Underground rough in for new server ok cover
ELE14-02408 Final9/29/20149/30/20149/30/2014 11:38:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
GCE14-00162 GCE-Temporary Service9/29/20149/30/20149/30/2014 10:52:02 AMAPASS
Terry ###-#### t/s u/g n ok
ELE14-02702 Electrical Rough-In9/29/20149/30/20149/30/2014 10:24:21 AMAPASS
Please call Stuart 30 min ahead of inspection. Inspection requested via web by Stuart Welton AC rough in ok
ELE14-02702 Final9/30/20149/30/20149/30/2014 10:24:05 AMPPASS
Please call Stuart 30 min ahead of inspection. Inspection requested via web by Stuart Welton AC Final ok
ELE14-01875 Electrical Rough-In9/29/20149/30/20149/30/2014 10:01:42 AMAPASS
Please call when on way so I can have someone meet you there. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan Check on final outlet spacing for counter for pass through window to back entry. rough in ok cover
ELE13-02572 Final9/29/20149/30/20149/30/2014 9:43:11 AMAPASS
casey Phone #: ###-#### Final ok
ELE14-02134 Final9/29/20149/30/20149/30/2014 9:20:32 AMAFAIL
Key is really hard to work. Key under closest paver. If you just pull on front door it opens locked or not. Phone #: ###-#### Inspection requested via web by mike brown 408.4 Field Identification Required.
(A) Circuit Directory or Circuit Identification. Every
circuit and circuit modification shall be legibly identified as
to its clear, evident, and specific purpose or use.
400.8 Uses Not Permitted. Unless specifically permitted
in 400.7, flexible cords and cables shall not be used for the
following:
(1) As a substitute for the fixed wiring of a structure. Feed for paddle fan
422.30 General. A means shall be provided to simultaneously
disconnect each appliance from all ungrounded
conductors in accordance with the following sections of
Part III. Heater
ELE14-02651 Final9/30/20149/30/20149/30/2014 8:35:09 AMPPASS
Final ok