Inspections for the day of: Tuesday, September 30, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00205 INSP-Sprinkler Rough-in9/30/20149/30/20149/30/2014 5:11:29 PMPPART
UG fire supply line approved for cover from the point of connection at the property line to the building stem wall. *Note- ductile riser and associated thrust block are incomplete at this time. Refer to dated notes on plan.
BLD14-01432 FIRE-Final Inspection9/30/20149/30/20149/30/2014 1:59:28 PMPPASS
Life safety inspection passed. PFE and address numbers posted while on site.
FIR14-00516 INSP-Sprinkler Rough-in9/29/20149/30/20149/30/2014 1:40:06 PMAPART
Overhead work at the grid ceilings passed rough-in. Need to repair/patch holes at the deck where new hangers are installed. One upright head at the NE corner open gym area needs relocated, also missing coverage at ductwork obstruction NE corner.
FIR14-00386 INSP-Final Inspection9/29/20149/30/20149/30/2014 1:37:18 PMAPASS
Correction items completed. Fire sprinkler permit finaled.
BLD14-01689 FIRE-Final Inspection9/29/20149/30/20149/30/2014 12:13:31 PMAPASS
Noted correction items verified for completion. Life safety final approved.
FIR14-00702 INSP-Sprinkler Rough-in9/29/20149/30/20149/30/2014 11:24:53 AMAPART
Scope of fire sprinkler work approved for cover at the sheetrock lids.
FIR14-00669 INSP-Sprinkler Rough-in9/29/20149/30/20149/30/2014 10:58:49 AMAPART
Okay to cover overhead fire sprinkler modifications at the grid ceilings within the tenant remodel area.
FIR14-00519 INSP-Conference9/29/20149/30/20149/30/2014 10:37:56 AMADONE
On site conference with contractor regarding new fire alarm work, duct smoke detection, notification, remote annunciator, knox box, and manual pull stations. Plan modification recommended for proposed changes.