Inspections for the day of: Friday, September 30, 2016.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03075 Rough-In Permanent Service9/29/20169/30/20169/30/2016 2:00:42 PMPPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson
Rough in ok cover p/s u/g n ok
ELE16-02180 Final9/29/20169/30/20169/30/2016 10:42:41 AMAFAIL
Please Mitch 30 minutes prior. Phone #: ###-#### Inspection requested via web by Mitch Whited
210.12- All outlets in bedroom areas shall have AFCI protection. Lighting not protected.
404.8- Circuit directory shall be complete.
406.12- All receptacle outlets installed in basement shall be tamper resistant type. All need replaced.
ELE16-02525 Electrical Rough-In9/29/20169/30/20169/30/2016 9:42:09 AMAPASS
This is a ceiling inspection for cover. Calvin will be there ###-####. Phone #: ###-#### Inspection requested via web by Clay Morgan Grid rough in ok cover