Inspections for the day of: Friday, September 30, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-01124 FIRE-Final Inspection9/30/20169/30/20169/30/2016 2:31:11 PMPPASS
Final life fire safety inspection passed/complete.
BLD16-03092 FIRE-Final Inspection9/29/20169/30/20169/30/2016 1:28:25 PMAPASS
Previously noted items addressed/repaired, no modifications to fire sprinklers, fire sprinkler systems have current inspection tags, no modifications to fire alarms, commercial hood fire suppression system has a current inspection tag, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00602 INSP-Final Inspection9/29/20169/30/20169/30/2016 12:53:19 PMPCANC
Final inspection of Pharmacy smoke detectors and dropping of Fire Fly, please call with as much notice as possible so we can contact the Overhead Door Company as well. Phone #: ###-#### >> Inspection requested via web by Jeremy Berg Inspection cancelled from web by: Jeremy Berg
BLD15-04452 FIRE-Final Inspection9/29/20169/30/20169/30/2016 12:49:17 PMAPART
Partial final inspection for life safety complete, fire department inspection still needs to happen for the fuel pumps/emergency shutoff. No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Life fire safety can be signed off as complete after the fire department inspection for the fuel tanks/pumps is passed and complete.
BLD14-02741 FIRE-Final Inspection9/28/20169/30/20169/30/2016 12:09:38 PMAPART
Final for fire life safety cannot be completed until fire sprinkler and fire alarm permits are finaled, both FIR permits still have some work to be completed. Emergency lighting has been tested, fire extinguishers are in place with current inspection tags and door closers have been tested. After the FIR permits are finaled then life fire safety can be finaled.
FIR15-00561 INSP-Final Inspection9/29/20169/30/20169/30/2016 12:07:26 PMPCANC
Final fire sprinkler inspection will be rescheduled to coincide with tamper switch wiring completion , tamper switches on backflow and fire pump control valve were not in place. Tamper switches were installed while alarm inspection was happening but still need to be wired into the alarm system.
FIR15-00313 INSP-Final Inspection9/29/20169/30/20169/30/2016 12:04:37 PMPPASS
Underground supply final inspection passed/complete.
BLD14-02802 FIRE-Final Inspection9/28/20169/30/20169/30/2016 12:03:32 PMAPASS
No fire sprinklers, no fire alarms. Final life fire safety inspection for this permit passed/complete.
FIR15-00574 INSP-Final Inspection9/29/20169/30/20169/30/2016 12:01:09 PMAPART
Partial final complete for alarm system. Audio visual devices and photo smoke detectors tested on every floor, AHU shutdown tested for rooftop untis. Tamper switches needed to be added to the fire pump isolation valve as well as backflow, tamoers were installed at time of inspection but will ned to be wired up. Wood beam in ballroom was blocking flash from the ceiling mounted strobe, two additional strobes will be mounted and tested during next inspection.
FIR16-00593 INSP-Sprinkler Rough-in9/29/20169/30/20169/30/2016 8:53:17 AMACANC
Due to scheduling issues, inspection will be completed on 03OCT2016.
FIR16-00582 INSP-Sprinkler Rough-in9/29/20169/30/20169/30/2016 8:52:56 AMACANC
Due to scheduling issues, inspection will be completed on 03OCT2016.
FIR16-00546 INSP-Sprinkler Rough-in9/30/20169/30/20169/30/2016 8:23:19 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball