Inspections for the day of: Monday, September 30, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03512 Pressure Test9/30/20199/30/20199/30/2019 4:01:33 PMPPASS
-20lb gas pressure test ok
MEC19-03512 Rough-in9/27/20199/30/20199/30/2019 4:00:46 PMPFAIL
Phone #: ###-#### Inspection requested via web by Michael Stimpson
-outside air cant terminate at the asphalt roof and is within 10' of exhausts
- need to see transfer/return into each bedroom
- range hood venting needs sealed
- return ducting needs sealed
- 5lb flue pressure test under 5lb
- install inert tape at gasline penetration
- add another dryer exhaust to permit
MEC19-04243 Final9/30/20199/30/20199/30/2019 3:51:59 PMPPASS
Please inspect from 2-4 PM. James Kibler ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace only co ok
MEC19-03744 Final9/30/20199/30/20199/30/2019 1:42:06 PMPNH
Phone #: ###-#### Inspection requested via web by terry Warden
- no access to home left notice on front door
MEC19-04112 Final9/30/20199/30/20199/30/2019 1:41:42 PMPFAIL
Phone #: ###-#### Inspection requested via web by terry Warden
- furnace ac coil co ok
- need to see an electrical permit issued for new A/C
MEC19-04322 Rough-in9/30/20199/30/20199/30/2019 1:40:55 PMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE
- R/I ok
MEC19-04322 Pressure Test9/30/20199/30/20199/30/2019 1:40:36 PMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE
- 20lb gas pressure test ok
- tagged meter location
MEC19-04268 Final9/27/20199/30/20199/30/2019 11:36:17 AMAFAIL
Please cal Gregg prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- need to see an electrical permit issued for mini split
MEC19-04203 Final9/27/20199/30/20199/30/2019 9:29:30 AMAPASS
Call ahead to Lisa @ ###-#### Phone #: ###-#### Inspection requested via web by Nicole Smith
- furnace ac coil co ok
MEC19-04291 Final9/30/20199/30/20199/30/2019 8:48:37 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- need to see gas pressure test/ gas piping added to permit and fees paid
- need to see co sensors installed near bedrooms
MEC19-04291 Pressure Test9/30/20199/30/20199/30/2019 8:47:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- 20lb gas pressure test ok
- tagged meter location
need to add gas pressure test/ gas piping to permit and pay fees
MEC19-00830 Mec-Aging Inspection9/30/20199/30/20199/30/2019 8:24:26 AM FAIL
Permit has not been active since inspection was cancelled on 3-5-19. Schedule final inspection with the homeowner.
MEC19-00880 Mec-Aging Inspection9/30/20199/30/20199/30/2019 8:22:57 AM FAIL
Need to schedule final inspection with homeowner. Permit has not been active since
3-1-19 when it passed a pressure test.